WARNING: This heater shall not be installed in a
room or space unless the required volume of indoor
combustion air is provided by the method described
in the National Fuel Gas Code, ANSI Z223.1/NFPA 54,
the International Fuel Gas Code, or applicable local
codes. Read the following instructions to insure proper
fresh air for this and other fuel-burning appliances in
your home.
Today's homes are built more energy efficient than ever. New materi-
als, increased insulation and new construction methods help reduce
heat loss in homes. Home owners weather strip and caulk around
windows and doors to keep cold air out and warm air in. During heat-
ing months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home needs
to breathe. Fresh air must enter your home. All fuel-burning appliances
need fresh air for proper combustion and ventilation.
Exhaust fans, fireboxes, clothes dryers and fuel burning appliances
draw air from the house to operate. You must provide adequate fresh
air for these appliances. This will insure proper venting of vented
fuel-burning appliances.
PROVIDING ADEQUATE VENTILATION
The following are excerpts from National Fuel Gas Code, ANSI Z223.1/
NFPA 54, Air for Combustion and Ventilation.
All spaces in homes fall into one of the three following ventilation
classifications:
1. Unusually Tight Construction
2. Unconfined Space
3. Confined Space
Information on page 7 through 9 will help you classify your space
and provide adequate ventilation.
Unusually Tight Construction
Air that leaks around doors and windows may provide enough fresh
air for combustion and ventilation. However, in buildings of unusually
tight construction, you must provide additional fresh air.
Unusually tight construction is defined as construction where:
a. walls and ceilings exposed to outside atmosphere have a con-
tinuous water vapor retarder with a rating of one perm (6 x 10
kg per pa-sec-m
) or less with openings gasketed or sealed and
2
b. weather stripping has been added on openable windows and
doors and
c. caulking or sealants are applied to areas such as joints around
window and door frames, between sole plates and floors, be-
tween wall-ceiling joints, between wall panels, at penetrations
for plumbing, electrical and gas lines and at other openings.
If your home meets all three criteria above, you must provide
additional fresh air. See Ventilation Air From Outdoors, page 7.
If your home does not meet all three criteria above, proceed to
Determining Fresh-Air Flow for Firebox Location.
6
AIR FOR COMBUSTION AND VENTILATION
Confined and Unconfined Space
The National Fuel Gas Code, ANSI Z223.1/NFPA 54 defines a confined
space as a space whose volume is less than 50 cubic feet per 1,000
Btu per hour (4.8 m
pliances installed in that space and an unconfined space as a space
whose volume is not less than 50 cubic feet per 1,000 Btu per hour
(4.8 m
in that space. Rooms communicating directly with the space in which
the appliances are installed*, through openings not furnished with
doors, are considered a part of the unconfined space.
* Adjoining rooms are communicating only if there are doorless
passageways or ventilation grills between them.
DETERMINING FRESH-AIR FLOW FOR HEATER LOCATION
Determining if You Have a Confined or Unconfined Space
Use this work sheet to determine if you have a confined or unconfined
space.
Space: Includes the room in which you will install heater plus any
adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height).
2. Multiply the space volume by 20 to determine the maximum Btu/
3. Add the Btu/Hr of all fuel burning appliances in the space.
-11
Astria.US.com
per kw) of the aggregate input rating of all ap-
3
per kw) of the aggregate input rating of all appliances installed
3
Length x Width x Height = __ cu. ft. (volume of space)
Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling
height) = 3168 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with grills or
openings, add the volume of these rooms to the total volume of the
space.
Hr the space can support.
_____ (volume of space) x 20 = (Maximum Btu/Hr the space can
support)
Example: 3168 cu. ft. (volume of space) x 20 = 63,360 (maximum
Btu/Hr the space can support)
Vent-free heater
_____ Btu/Hr
Gas water heater*
_____ Btu/Hr
Gas furnace
_____ Btu/Hr
Vented gas heater
_____ Btu/Hr
Gas fireplace logs
_____ Btu/Hr
Other gas appliances* + _____ Btu/Hr
TotaL
= _____ Btu/Hr
* Do not include direct-vent gas appliances. Direct-vent draws
combustion air from the outdoors and vents to the outdoors.
Example:
Gas water heater
40,000 Btu/Hr
Vent-free heater + 39,000 Btu/Hr
Total
= 79,000 Btu/Hr