Akytec ITP14-G Benutzerhandbuch - Seite 5

Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Messgeräte Akytec ITP14-G herunter. Akytec ITP14-G 10 Seiten. Universal process indicator

Signal cables should be routed separately or screened from the supply cables.
NOTICE
Only a shielded cable may be used for signal lines.
The electrical connections are shown in Fig. 5.2-5.4, the terminal assignments in Table
5.1.
Connect the power supply to the terminals 24V+ / 24V–
Ensure that the device is provided with its own power supply line and electric fuse I = 0.5
A.
The maximum conductor cross-section is 1 mm². Wires should be stripped for approx. 8-
10 mm.
5.1.1
Table 5.1 Terminal assignment
5.1.2
The NPN transistor output is designed to control the low voltage relay up to 42 V DC / 200
mA
As a precaution against inadvertent current reversal on output, a parallel diode (U
NOTICE
≥ 1.3U, I
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 ·

Input

Fig. 5.2 Current sensor wiring
Designation
24VDC -
24VDC +

Output

≥ 1.3I) is usually included in the output circuit.
VD
Fig. 5.1 Mounting
Fig. 5.3 Voltage sensor wiring
Description
Power supply
DO-
Output -
DO+
Output +
COM
Common -
U+
Voltage input +
I+
Current input +
VD
www.akytec.de
4