on for 10 seconds, the whole unit will stop
operation. The LED will display "P2" and the
water full lamp will flash at 5Hz. After you have
clear the problem, you should unplug the unit
and plug again. Then the unit will be ready to
operate.
2.2.4.4.5 When the unit is standing by, if the unit
displays "P1", the pump will not operate. After
the problem is cleared, the unit will be ready to
operate. But if you push the power button, the
unit will shut the "P1" display and shut down.
2.2.5 Fan-only Mode Function Requirement
2.2.5.1 The compressor and outdoor fan are OFF at
Fan-only mode.
2.2.5.2 The speed of indoor fan can be optionally
chosen as High/Mid/Low.
2.2.6 Cooling Mode Function Requirement
2.2.6.1 The speed of indoor fan can be optionally
selected as High/Mid/Low.
2.2.6.2 The compressor operate as:
O
C
ro om t em per ature (TA)
Comp ressor O N
TS+1
TS
Co mpressor O FF
Temp down
2.2.7 Drying mode
2.2.7.1 When the unit starts to operate in Drying
mode, the compressor will start while the room
temperature is over 13
started, the compressor will operate as:
O
C
ro om t em per ature (TA)
Comp ressor and outd o or
fan O N
o
15 C
o
13 C
Co mpressor and
ou t door fan OFF
Temp down
2.2.7.2 The indoor fan will operate with high
speed. The outdoor fan will operate with
compressor.
2.2.8 Heating mode
2.3 TROUBLESHOOTING GUIDE
In general, possible trouble is classified in three kinds. One is called Starting Failure which is caused from
an electrical defect, another is ineffective Air Conditioning caused by a defect in the refrigeration circuit and
improper application, and the other is called the Structure Damage.
Temp up
o
C. After the compressor
Temp up
Service manual for K1 portable Series
2.2.8.1 The speed of indoor fan can be optionally
chosen as High/Mid/Low.
2.2.8.2 Electric heater operate as :
O
C
ro om t em per ature (TA)
Elec t ric h eater O FF
TS+1
TS
El ec tric h eater O N
Temp down
2.2.9 Temperature display
2.2.9.1 The setting temperature will be displayed in
Cooling and Heating mode. The room
temperature will be displayed in Drying and Fan
only mode.
2.2.9.2 The setting temperature range is from 17
o
o
to 30
C or 62
F to 88
o
range is from 10
C to 35
room temperature is lower than 10
o
display will be 10
C or 48
2.2.10 Timer Function
2.2.10.1 The maximum length of Timer is 24 hours
and the minimum is 0.5 hours.
2.2.10.2 TIMER ON function: first turn OFF the unit,
the unit will be automatically ON at the set time.
2.2.10.3 TIMER OFF function: first turn ON the unit,
the unit will be automatically OFF at the set time.
2.2.10.4 TIMER ON/OFF function (ON TIMER is
earlier than OFF TIMER): first turn OFF the unit,
it will be automatically ON at set time, and later
be OFF at the set time.
2.2.10.5 TIMER OFF/ON function (OFF TIMER is
earlier than ON TIMER): first turn ON the unit, it
will be automatically OFF at set time, and later
be ON at the set time.
2.2.10.6 Timer function execution is applicable upon
one operation only.
2.2.10.7 Timer precision is less than 15 minutes.
2.2.11 Auto restart function
In case of a sudden power failure, this function
automatically sets the unit to previous settings
before the power failure when power returns.
Temp up
o
F. The display temperature
o
o
o
C or 48
F to 98
F. If the
o
o
C or 48
o
F.
o
C
F, the
5