GSCM-mini-P
The GSCM-mini-P's K1 &K2 relay contact wire in parallel with each other and the generators Start/Stop push button. The
GSCM-mini-P's K1 relay provides the turn on one second pulse and then 2 seconds later provides a second pulse to start the
generator. The K2 relay contact provides the stop pulse to shutdown the generator. The GSCM-mini_p monitors the AC
output to know when the generator has started. The Champion ECU provides up to six starting attempts before going into a
fault condition.
The GSCM-mini-P's terminal #6 is not connected. Terminal #3 (+12vdc) is connected to Samles's normally open relay contact,
and the common contact wires back to terminal #5 on the GSCM-mini-P. The generators AC output is wired to terminals # 9 &
10 providing the run feedback signal. An optional Battery tender/charger is not needed for this option.
The GSCM-mini-P accepts Samlex's two wire relay contact (maintained run signal) and provides a one second start /stop pulse
as outlined on page 5 GSCM-mini-P opion#1.
www.atkinsonelectronics.com
Circuit Board Division
800.261.3602
Champion Model # 100573 4KW w/Wireless Remote
11