Anywire ASLINKER BL2LN87SB-02DS-CC20 System Produkthandbuch - Seite 9
Blättern Sie online oder laden Sie pdf System Produkthandbuch für Adapter Anywire ASLINKER BL2LN87SB-02DS-CC20 herunter. Anywire ASLINKER BL2LN87SB-02DS-CC20 20 Seiten.
[Name of Each Part]
Transmission line connection wire
Red: DP
Black: DN
Green: 24V
White: 0V
[Connection Method]
■Example of tting the LP connector at the end of transmission line
Applicable LP connector: LP4-WW-10P
Wire color
Pin No.
Black (DN)
Red (DP)
White (0V)
Green (24V)
Place the wires in the grooves so
that the black wire (DN) is on the
hinge side of the cover, fold A over B
and engage the hook C to fasten it.
[Various Settings]
Address setting
■Common procedure for address writer operation
Be sure to connect to the AnyWireASLINK master unit to use.
ARW-04 (address writer) of Rev. (Ver.) 1.01 or later version is required for address setting.
For the details of the operating method, refer to the product guide of ARW-04.
Connect this unit to the AnyWireASLINK master unit.
With the transmission signal (DP/DN) and power supply (24V/0V) being connected, set
parameters with the address writer.
Transmission
signal
AnyWireASLINK
master
24V DC*
* For the power supply to be
connected, be sure to use
a 24V DC stabilized
power supply.
LED indicators
Red: DP
Black: DN
Green: 24V
1
White: 0V
2
3
4
The condition in which
the cover is tted.
Ensure that the hooks
① and ② are engaged.
B
A
Cover
C
Parameter setting
Red: DP
Black: DN
Green:
White: 0V
24V
-BL2LN87SB02D*CC20 9/20-
LINK
: Transmission indicator (Green)
IN0
: Input indicator (Orange)
IN1
: Input indicator (Orange)
ALM
: Alarm indicator (Red)
Setting port
Pressure-bond using a
dedicated tool by guiding the
metal bracket on the connector
body into the hole of the cover.
① ②
Dedicated tool: LP-TOOL
Make sure that the 24VL wire (brown) and 0VL wire
(blue) are not short-circuited while power is supplied.
LINK
IN0
IN0
IN1
ALM
IN1
Short-circuit may cause a fault of the equipment.
After pressure-bonding, ensure
that the hooks ③ to ⑥ are
securely engaged.
③ ④
⑤ ⑥
CAUTION
Input line
connection wires
Brown: 24VL
Black: IN0
Blue: 0VL
Brown: 24VL
Black: IN1
Blue: 0VL