Apollo ORB-OH-13001-APO Produkthandbuch

TECHNICAL DATA

All data is supplied subject to change without notice.
Specifications are given at 23°C and 50% relative humidity unless otherwise stated.
DETECTOR OPERATING PRINCIPLES
Principle of detection:
Photo-electric detection of light scattered by smoke particles
over a wide range of angles. The optical arrangement
comprises an infra-red emitter with a prism and a photo-
diode at 90° to the light beam with a wide field of view.
The detector's microprocessor uses algorithms to process
the sensor readings. The heat sensing element increases the
sensitivity of the detector as the temperature rises.
Sampling frequency:
Once every 4 seconds
ELECTRICAL
Supply voltage:
8.5—33V DC
Supply wiring:
2 wires, polarity sensitive
Maximum polarity reversal:
200ms
<20 seconds
Power-up time:
Minimum 'detector active' voltage: 6V
Switch-on surge current at 24V: 95µA
Average quiescent current at 24V: 95µA
Alarm current:
At 12 volts
At 24 volts
Alarm load:
600Ω
Holding voltage:
5–33V
Minimum holding current:
8mA
Minimum voltage to light
5V
alarm LED:
Alarm reset voltage:
<1V
Alarm reset time:
1 second
Remote output LED
1.2kΩ connected to negative supply
(–) characteristic:
MECHANICAL
Material:
Detector and base moulded in white polycarbonate.
Alarm Indicator:
Integral indicator with 360° visibility
(See Table 3 on page 13)
Dimensions:
97mm diameter x 42mm height
100mm diameter x 57mm height (in base)
Weight:
Detector
Detector in base
ENVIRONMENTAL
Temperature:
Operating and storage temperature
Humidity:
0% to 98% relative humidity (no condensation)
Wind speed:
Unaffected by wind
Atmospheric pressure:
Insensitive to pressure
IP rating to EN 60529: 1992*: 23D
Electromagnetic Compatibility: The detector meets the requirements of EN 61 000-6-3
for emissions and BS EN50 130-4 for susceptibility.
*The IP rating is not a requirement of EN 54 since smoke detectors have to be open in order
to function. An IP rating is therefore not as significant as with other electrical products.
CONVENTIONAL DETECTORS
–40°C to +70°C
(no condensation or icing)
20mA
40mA
9
80g
140g