Apollo Orbis CR Produkthandbuch - Seite 7
Blättern Sie online oder laden Sie pdf Produkthandbuch für Rauchmelder Apollo Orbis CR herunter. Apollo Orbis CR 16 Seiten.
ENVIRONMENTAL
PERFORMANCE
Orbis optical detectors operate over a
broad range of voltages at extremes of
temperature. Thus the operating voltage
is 8.5V to 33V at –40° to +70°C, a unique
achievement for a conventional smoke
detector.
www.acornfiresecurity.com
All data is supplied subject to change without notice.
Specifications are given at 23°C and 50% relative humidity unless otherwise stated.
DETECTOR OPERATING PRINCIPLES
Principle of detection:
Sampling frequency:
ELECTRICAL
Supply voltage:
Supply wiring:
Maximum polarity reversal:
Power-up time:
Minimum 'detector active' voltage: 6V
Switch-on surge current at 24V: 95µA
Average quiescent current at 24V: 95µA
Alarm current:
Alarm load:
Holding voltage:
Minimum holding current:
Minimum voltage to light
alarm LED:
Alarm reset voltage:
Alarm reset time:
Remote output LED
(–) characteristic:
MECHANICAL
Material:
Alarm Indicator:
Dimensions:
Weight:
ENVIRONMENTAL
Temperature:
Humidity:
Wind speed:
Atmospheric pressure:
IP rating to EN 60529: 1992*: 23D
Electromagnetic Compatibility: The detector meets the requirements of EN 61 000-6-3
*The IP rating is not a requirement of EN 54 since smoke detectors have to be open in order
to function. An IP rating is therefore not as significant as with other electrical products.
www.acornfiresecurity.com
CONVENTIONAL DETECTORS
TECHNICAL DATA
Photo-electric detection of light scattered by smoke
particles over a wide range of angles. The optical
arrangement comprises an infra-red emitter with a prism
and a photo-diode at 90° to the light beam with a wide
field of view. The detector's microprocessor uses algorithms
to process the sensor readings.
Once every 4 seconds
8.5—33V DC
2 wires, polarity sensitive
200ms
<20 seconds
At 12 volts
At 24 volts
600Ω
5–33V
8mA
5V
<1V
1 second
1.2kΩ connected to negative supply
Detector and base moulded in white polycarbonate.
Integral indicator with 360° visibility
(See Table 3 on page 13 for details of flash rate)
97mm diameter x 31mm height
100mm diameter x 46mm height (in base)
Detector
Detector in base
Operating and storage temperature
0% to 98% relative humidity (no condensation)
Unaffected by wind
Insensitive to pressure
for emissions and BS EN50 130-4 for susceptibility.
20mA
40mA
75g
135g
–40°C to +70°C
(no condensation or icing)
7