Apollo XPander XPA-CB-12034-APO Handbuch für die Inbetriebnahme - Seite 7
Blättern Sie online oder laden Sie pdf Handbuch für die Inbetriebnahme für Rauchmelder Apollo XPander XPA-CB-12034-APO herunter. Apollo XPander XPA-CB-12034-APO 19 Seiten. Diversity loop interface module
Auch für Apollo XPander XPA-CB-12034-APO: Installationshandbuch (2 seiten), Installationshandbuch (2 seiten)
Initial power up screen
Multiple Interfaces
If more than 1 interface is being used, refer to Appendix B on page 14 before logging on the devices and complete
the checklist on the lid. Interfaces are numbered from 1 to 5. This is not the loop address, it is the frequency ID.
For fault free operation, the interfaces must have the channels set correctly. To do this the interfaces must be
numbered so that the nearest interface to 1 is 2 and the nearest interface to 2 is 3 etc. Start at one end of the site
plan and continue in this manner until all 5 have been labelled. Use the table in Appendix B on page 14 to set the
channels on the interfaces.
Logging on interfaces
Up to 31 wireless detectors or alarm signalling devices may be assigned to a single interface. Prior to adding
devices to the Interface, batteries must be inserted, the power jumper positioned correctly and the mounting
plates fitted. During the device log-on routine, the interface will request confirmation of the device serial number.
This is to be found on the side of the radio module. The XPERT address card must be fitted prior to assigning a
device to the interface. In the case of sounders or sounder visual indicators the tone must be selected using the
5-segment DIL switch on the base of the sounder or sounder visual indicator.
Note: I/O Units and the Combined Sounder Visual Indicator Base do not have an XPert card, the addressing is set
by a DIL switch.
No. of devices
No. of logged
logged onto
on devices in
interface
alarm condition
DEV 00 AL 00 FT 00
© Apollo Fire Detectors Limited 2015
No. of logged on
devices in fault
condition
7