SYSTEM CHECKOUT:
Perform these tests after the wiring and option selections described in the previous sections have been completed.
1. Connect the battery in the No. 1021/4021 to the Molex connector on the panel's RED and BLACK leads.,
Note: Check that the RED Arming Status LED at the No. 5240 is not lit. If it is lit, it should be extinguished by keying
the ARM/DISARM code.
,,--
2. Plug the transformer into a 120V. AC outlet that is ON 24 hours a day. The A.C. POWER LED should light.
3. Observe the ZONE STATUS LEDs. None will be lit if the protective loops are properly wired and all contacts are
properly set.
4. When all ZONE STATUS LEDs are out, do the following and observe the appropriate LED light in each case.
a. Open the PERIMETER ZONE loop momentarily. The PERIMETER ZONE LED should light while the loop is
open. Repeat for the INTERIOR and DELAY ZONE loops and LEDs.
b. Short the Perimeter Zone momentarily. The Perimeter Zone LED should light while the loop is shorted.
Repeat for the Interior Zone loop and LED.
5. Observe the FlRE LED. It should be OFF if the protective loop and detector power circuits are properly wired.
6. Check the FIRE circuit operation as follows:
a. Disconnect one wire of the Fire loop. The FHE LED on the No. 1021/4021 should flash and an intermittent
buzz should be heard from the No. 5240(s).
b. Re-connect the Fire loop wire. The FIRE LED should go out and the intermittent "buzz" should cease, indicat-
ing zone restore.
c. Momentarily short the Fire loop. A fire alarm should be triggered accompanied by a loud steady siren sound
from both the internal (in the No. 4021) and external (if used) speakers. In addition. the FIRE LED should
be lit steady.
Silence the alarm by momentarily activating the FIRETESTRESET switch to the RESET position.
Note: The battery may not be fully charged. If this test is tried with a low battery there will not be enough
power to sound the externalsirens. Let the unit charge (transformer plugged in) for at least one-haff
hour if the battery is low.
7. Test the Panic Circuit by momentarily shorting terminals 9 and 10 or by operating a panic switch. The interior (in
the No. 4021) and exterior speaker should sound (warbling siren sound) if the audible option is selected and the
\
No. 5240's GREEN Loop Status LED should turn off. These conditions continue after the short is removed. Reset
:t-
the circuit by keying the arm/disarm code' and then turn on the LED by momentarily activating the FIRE TEST/
RESET switch to the RESET position.
*Note: Cutoff will be immediate if the system was armed and will occur after 3 seconds if the system
was disarmed.
. 8.;Arm the syr&n by entering the arming code at the keypad. The'RED Arming Status LED shoirl;dligtitsteadily.
Immediately depress the "0" key and the Arming Status LED will flash, indicating that the system has been armed
with the Interior Zone turned off.
9. Depress the ENTRY DELAY OFF (INSTANT) Switch on the No. 1021(4921). The LED to the left of it should light.
Disarm the system. Note that the ENTRY DELAY (INSTANT) and the Arming Status LEDs go out, indicating a
restoral of the entry delay. The Interior Zone has also been restored.
10. All the zone contacts may now be checked by disturbing each contact in each zone and observing the
status indicators.
11. Arm the system and disturb a contact. The warbling siren should sound.
12. Disarm the system.
13. Check the operation of the supplementary output triggers.
14. Momentarily disconnect the AC power to the system. The A.C. POWER LED on the No. 102114021 should go
out but the system should remain operable.
15. Arm the system and simulate leaving the premises by following the procedure given in the
OPERATION Section.
16. Simulate entering the premises and disarm the system by following the procedure given in the
OPERATION Section.