6139AV KEYPAD AUDIO CONNECTION
FOR 2-WAY VOICE OPERATION
1. Follow the instructions for WIRING AND MOUNTING above.
2. The 6139AV requires a shielded 2-wire connection to a Voice
Interface Module (VIM). Splice the flying leads of the supplied
SA550AB Audio Bus connector to this shielded cable, then plug
the connector into the 6139AV keypad's J5 connector located
along the lower right-hand side of the PC board.
IMPORTANT: Connect the shield at the VIM module, not
at the keypad, as shown in the VIM's wiring diagram.
KEYPAD
6139AV
USE SA550AB AUDIO CONNECTOR SPLICED TO
SHIELDED CABLE WHEN USING 6139AV KEYPAD
Setting the keypad Address (no DIP switches)
The keypad can be set for an address of 0-31 (the keypad will not
accept entries greater than 31) which is stored in EEROM memory.
The keypad's default address is 31 (non-addressable mode–some
early versions of 6139/6139R default to 11).
NOTE: For operation with the VIM, the 6139AV can only be
set to addresses 01–15. Address 00 is reserved for a two-line
alpha non–voice keypad.
To change the keypad's address, do the following:
1. Enter address mode: Power-up (plug-in) the keypad. Within 60
seconds of power-up, press and hold down the [1] and [3] keys at
the same time for 3 seconds. (If unable to enter address mode,
power-up and try again).
The current keypad address will be displayed, and the cursor will
be under the "tens" digit. If 10 seconds have passed with no key
entry, the keypad automatically exits address mode. You must
power down, power-up and start address mode again.
NOTE: The keypad will not enter address mode if the panel
to which it is connected is in programming mode.
2. Set the current address to "00": Press [0] to clear the current
"tens" digit. The cursor will move to the "ones" digit position.
Press [0] to clear the current "ones" digit. The cursor will move
back to the "tens" digit position
3. Enter the keypad's address: Enter the proper "tens" digit of
the keypad's address. The cursor will move to the "ones" digit
position. Enter the proper "ones" digit of the keypad's address.
Note that address "31" sets the keypad to non-addressable mode.
4. Exit address mode:
Press [*] to save the displayed address and exit address mode.
REFER TO INSTALLATION INSTRUCTIONS FOR THE CONTROL PANEL FOR DETAILS ON LIMITATIONS OF THE ENTIRE ALARM SYSTEM.
Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affili ates ("Seller"), 165 Eileen Way, Syosset, New York 11791, warrants its products to be
in conformance with its own plans and specifications and to be free from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the
product or, for products not having an Ademco date stamp, for 12 months from date of original purchase unless the installation instructions or catalog sets forth a shorter period, in which case the
shorter period shall apply. Seller's obligation shall be limited to repairing or replacing, at its op tion, free of charge for materials or labor, any product which is proved not in compliance with Seller's
specifications or proves defective in materials or workmanship under normal use and service. Seller shall have no obligation under this Limited Warranty or otherwise if the product is altered or
improperly repaired or serviced by anyone other than Ademco factory service. For warranty service, return product transportation prepaid, to Ademco Factory Service, 165 Eileen Way, Syosset, New
York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE OR OTHERWISE, WHICH EXTEND BEYOND THE
DESCRIPTION ON THE FACE HEREOF. IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY
OTHER WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER'S OWN
NEGLIGENCE OR FAULT.
Seller does not represent that the products it sells may not be compromised or circumvented; that the products will prevent any personal injury or property loss by burglary, robbery, fire or otherwise;
or that the products will in all cases provide adequate warning or pro tection. Customer un derstands that a properly installed and maintained alarm may only reduce the risk of a burglary, robbery, fire
or other events occurring without providing an alarm, but it is not insurance or a guarantee that such will not occur or that there will be no personal injury or property loss as a result.
CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY, PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE
WARNING. HOWEVER, IF SELLER IS HELD LIABLE, WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED WARRANTY OR OTHERWISE,
REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM LIABILITY SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE OF THE PRODUCT, WHICH SHALL BE THE COMPLETE
AND EXCLUSIVE REMEDY AGAINST SELLER. This warranty replaces any previous warranties and is the only warranty made by Seller on this product. No increase or alteration, written or verbal, of
the obligations of this Limited Warranty is authorized.
www.PDF-Zoo.com
N6752V6 6/97
ALL KEYPADS CONNECT
TO CONTROL'S KEYPAD
TERMINALS
SHIELD
CONNECT 6139 AV KEYPADS
TO VIM AUDIO TERMINALS
(CONNECT SHIELD AT VIM
TERMINAL, NOT AT KEYPAD)
ADEMCO LIMITED WARRANTY
firealarmresources.com
Viewing the Keypad Address
Press and hold down the [1] and [3] keys at the same time for about
3 seconds. The current address is displayed. No key entry is
allowed. Press any key to exit or wait 10 seconds to exit viewing
mode.
6139AV Keypad Audio Level Selection
The "talk"
and "vox" volume of the 6139AV keypad can be
programmed for "high," "medium," or "low." The factory default is
"high."
1. Enter the keypad's programming mode by pressing and holding
down the [1] and [3] keys at the same time for 3 seconds. The
keypad's address is displayed.
2. Press and hold hold down the "D" key for 2 seconds. The current
"talk" level is displayed (high,medium, or low).
3. Press the [#] key repeatedly to toggle the level settings from high
to medium to low until the desired level is displayed.
4. Press and hold the "D" key until the "vox" level is displayed
5. Repeat step 3.
6. Press (*) to exit keypad programming mode.
Notes:
The keypad returns to normal mode if no key is pressed for 30
seconds.
Powering down the keypad does not change the level setting.
Specifications:
Physical
6128: 4-3/4"H x 5-3/4"W x 1"D (121mm x 146mm x 25.4mm)
6137/6137R:
4-3/4"H x 6-1/4"W x 1"D (121mmx 159mm x 26mm)
6138/6139/6139R/6139AV: 4-3/4"H x 6-3/4"W x 1-1/4"D
(121mm x 159mm x 32mm)
Wiring:
Red:
+12VDC
(all Keypads) Black:
ground.
Blue:
If present, not used.
Green:
Data to control panel.
Yellow:
Data from control panel
Current:
6128:
30mA sounder on, 25mA standby, alarm sounder off.
6137/6137R: 85mA (ARMED LED lit, LCD backlight and sounder
on), reduces to 40mA when panel is operating in
standby mode (backlight off).
6139/6139R:
100mA (ARMED LED lit, LCD backlight and sounder
on), reduces to 40mA when panel is operating in
standby mode (backlight off).
6139AV:
200mA (Armed LED lit, LCD backlight and sounder
on); reduces to 55mA when panel is operating in
standby mode (backlight off).
Displays:
6138:
1 x 16 alpha-numeric supertwist LCD, backlit.
6139/6139R/
6139AV:
2 x 16 alpha-numeric supertwist LCD, backlit.
6128, 6137:
Fixed-Word LCD (6137 backlit).
Sounder:
Piezo-electric (fire alarm is loud, pulsing single tone;
(all Keypads) burglary alarm is loud, continuous, dual tone).
6139AV:
0.2W speaker
ALARM DEVICE MANUFACTURING CO.
A DIVISION OF PITTWAY CORPORATION
165 EILEEN WAY, SYOSSET, NEW YORK 11791
COPYRIGHT © 1997 PITTWAY CORPORATION