AutomationDirect Productivity2000 P2-HSI Handbuch - Seite 2

Blättern Sie online oder laden Sie pdf Handbuch für Kontrolleinheit AutomationDirect Productivity2000 P2-HSI herunter. AutomationDirect Productivity2000 P2-HSI 8 Seiten. High-speed pulse input

AutomationDirect Productivity2000 P2-HSI Handbuch

General Specifications

Module Type
Intelligent
Modules per Base
15 maximum*
I/O Points Used
None, mapped directly to tags in CPU
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC 60068-2-6 (Test Fc)
Shock
IEC 60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
>10MΩ @ 500VDC
Heat Dissipation
5.76 W
Enclosure Type
Open Equipment
Module Location
Any I/O slot in a Productivity2000 System
Field Wiring
Use ZIPLink Wiring System. See "Wiring Options" on page 4.
See the "EU Directive" topic in the Productivity Suite Help File.
EU Directive
Information can also be obtained at:
www.productivity2000.com
Weight
90g (3.2 oz)
UL 61010-1 and UL 61010-2-201 File E139594, Canada & USA
Agency Approvals
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-201 Safety)**
* Note: For complete system limits, please refer to the "Hardware and
Communication Limits" table in the Productivity Suite Help file, "Hardware
Configuration" topic (P050).
**Meets EMC and Safety requirements. See the D.O.C. for details.

Status LEDs

Fault Status LEDs
(F) 1, 2, 3 & 4 (one per status output)
Input LEDs
(IN) 1A, 1B, 1Z, 2A, 2B, 2Z, IN3 & IN4 (one per status input)
Output Status LEDs
(O) OUT1, OUT 2, OUT3 & OUT4
Note: Top row fault LED's blinking indicates loss of external power.
2
www.productivity2000.com

Status Output Specifications

Status Outputs
4 sink/source
Output Signal Type, per Channel Select
Current Sinking
Operating Voltage¹
5–24 VDC
Output Volts Maximum
36VDC
Output Current Maximum
500mA
Short circuit detect and current limit with automatic retry
Overcurrent Protection
for each output
Output Self Limiting Current
1.2 to 2.4 A
Max Inrush Current
Self limited
Output Voltage Drop
0.7 VDC @ 0.5 A
Thermal Protection
Independent over temperature protection each output
Output Voltage Clamp During Inductive
+45VDC
Switching
Maximum OFF to ON Response
25μs²
Maximum ON to OFF Response
25μs²
NOTES:
1. Operating voltage of current sourcing outputs must be no greater than external
power.
2. Measured at 5VDC operating voltage, 0.5 A load current.

Power Specifications

External Power
Maximum Voltage
Minimum Voltage
Current Consumption Excluding Outputs
Maximum Current Consumption Total of the 4
Status Outputs
Tech Support 770-844-4200
Current Sourcing
5–24 VDC¹
26.4 VDC¹
-20VDC
24VDC -15% / +10%, Class 2
26.4 VDC
20.4 VDC
50mA
2A