ADEMCO 5817CB Einbauanleitung - Seite 2

Blättern Sie online oder laden Sie pdf Einbauanleitung für Transmitter ADEMCO 5817CB herunter. ADEMCO 5817CB 2 Seiten. Wireless commercial / household transmitter
Auch für ADEMCO 5817CB: Einbauanleitung (4 seiten), Schnellstart-Handbuch (2 seiten), Handbuch für Installation und Einrichtung (2 seiten), Handbuch für Installation und Einrichtung (2 seiten)

ADEMCO 5817CB Einbauanleitung
6. Attach the case back to the mounting plate by sliding the keyhole slots in the case
back down onto the mounting plate's holding posts. The locking tab will click as the case
back locks in place. To disengage the unit from an installed mounting plate, insert a
small screwdriver into the mounting plate release hole, push down to retract the locking
tab, and push upward on the unit to disengage from posts.
Set the DIP switch (after the control panel has enrolled the transmitter's input IDs) for
7.
the desired primary loop characteristics, as described in the table below.
PRIMARY LOOP OPTIONS TABLE
DIP SWITCH POSITION
SWITCH
SETTING
1
2
ON
REPEATING
TRANSMISSION
(every 4 sec.)
UPON PRIMARY
SWITCH MUST
LOOP FAULT
ALWAYS BE
Use for high priority
IN THE
alarm, such as fire.
ON
OFF
SINGLE
POSITION
TRANSMISSION
PER PRIMARY
LOOP CHANGE-
OF-STATE
Notes:
a. In order for the control panel to enroll the transmitter, the DIP switches must
be set to OFF – ON – ON – OFF (see Diagram 2).
b. The Auxiliary loops are not affected by the DIP switch settings.
UL REQUIREMENT
1. If using one of the panel revisions shown in the following table, and programming the
5817CB as an Entry/Exit zone, you must enroll the tamper loop (loop 4) as a separate
zone, programmed for 24-hour response (e.g., zone type 5  Trouble-by-day/Alarm-by-
night).
Model #
Rev.
EPROM P/N
FA1600C
8
(WAVIS150FA-18)
Vista-32FB
3
(WAVIS32FB-13)
Vista-128FB
4
(WAVIS128FB-14)
Vista-128B
3
(WAVIS128B-13)
2. For UL Commercial Burglary installations, this transmitter must be used in conjunction
with the 5881ENHC RF Receiver.
WIRING CONNECTIONS
Connect the loop wiring to the unit's terminals before installing the battery (see Diagram 2).
Notes:
a. Primary loop 1 is a supervised loop and must have an end-of-line (EOL)
resistor (470K ohms, supplied) placed across the last sensor. Additionally, for
Primary loop 1, a contact device may not be installed more than 20 feet from the
transmitter.
b. If loop 2 is not going to be used, the magnet is not necessary.
c.
If loop 3 is not going to be used, no connection is needed across its terminals.
For UL household burglary and fire installations, the loop 3 contact device (if
used) may not be more than 3 feet from the transmitter.
BATTERY INSTALLATION/REPLACEMENT
1. Remove the transmitter's cover as described in Mounting Step 1.
2. Observe correct polarity and insert the battery provided into the battery holder
(see Diagram 2). Take care not to bend the antenna.
3
4
SWITCH MUST
SWITCH MUST
ALWAYS BE
ALWAYS BE
IN THE
IN THE
ON
OFF
POSITION
POSITION
- 2 -
firealarmresources.com
Note: Replace battery only with: Duracell DL123A, Sanyo CR123A,
Panasonic CR123A, Ademco 466, Varta CR123A, or Tekcell CR123A.
CAUTION:
Risk of fire, explosion, and burns. Do not recharge, disassemble,
heat above 212°F (100°C), or incinerate. Dispose of used batteries
promptly. Keep away from children.
3.
To replace the cover, engage the hooks along the top edge and snap shut.
SPECIFICATIONS
Dimensions
1-9/16"W x 3-1/2"H x 1-3/16"D (40mm x 89mm x 30mm)
Battery 3V Lithium (see BATTERY INSTALLATION/REPLACEMENT).
UL Listings:
Commercial Fire ...................................... UL864
Household Fire......................................... UL985
Household Burg ....................................... UL1023
Commercial Burg ..................................... UL365, UL609, UL634, UL1610
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the installer and frequent testing
by the user are vital to continuous satisfactory operation of any alarm system.
The installer should assume the responsibility of developing and offering a regular
maintenance program to the user, as well as acquainting the user with the proper operation
and limitations of the alarm system and its component parts. Recommendations must be
included for a specific program of frequent testing (at least weekly) to insure the system's
operation at all times.
FO R D ETA I LS O N LI M I TA TI O N S O F TH E EN TI R E A LA R M
C O N TR O L PA N EL' S I N STA LLA TI O N I N STR U C TI O N S FO R TH E R EC EIV ER / C O N TR O L W I TH
W H I C H TH I S D EV I C E I S U SED .
NOTE:
For UL commercial and household fire
installations, only one initiating device may be
connected to this transmitter. For UL commercial
burglary installations, multiple initiating devices
may be used as long as the devices all service
the same function such as door/window contacts,
motion or glassbreak detectors. All initiating
devices must be located within the same room.
THE DIP SWITCHES MUST BE
SET AS SHOWN DURING
ENROLLMENT BY THE CONTROL
WHITE AREA
INDICATES
SWITCH HANDLE
ON
ON
DIP
SWITCH
OFF
1
2
3
4
DIP SWITCH FOR PRIMARY LOOP OPTIONS
(SEE SETTINGS TABLE)
SHOWN SET FOR: 1. SINGLE TRANSMISSION
NOTE: SW2 MUST BE ON
SW3 MUST BE ON
COVER
SW4 MUST BE OFF
TAMPER
SWITCH
LOOP 3
TERMINALS
(AUX)
SLOT FOR
CONCEALED
WIRING ACCESS
CONTACT
Diagram 2. Transmitter, Cover Removed
SY STEM , R EFER TO TH E
MOUNTING
PLATE
HOLE
TAMPER SWITCH
HOLD DOWN
CONCEALED
WIRING
ENTRY
HOLE
Diagram 1. Mounting Plate
COVER
HOLDING
ANTENNA
SLOTS (2)
ALIGN MAGNET
WITH MARKS ON
CASE (2 PLACES)
LOOP 2
REED SWITCH
(AUX)
+
BATTERY
MAGNET
(OBTAIN
SEPARATELY)
1/2"
MAX.
PRIMARY
MOUNTING
LOOP 1
PLATE
TERMINALS
COVER
RELEASE
PRY-OFF
POINT
N.O.
N.C.
CONTACT
EOLR
470K ohms
DEVICE
DEVICE
5817CB-002-V1
- 3 -
CASE
HOLDING
POSTS
MOUNTING
PLATE HOLES
LOCKING
TAB
5817CB-001-V0