Input Specifications
Input Channels
Module Signal Input Range
Signal Resolution
Resolution Value of LSB
(least significant bit)
Data Range
Input Type
Maximum Continuous Overload
Input Impedance
Filter Characteristics
Sample Duration Time
All Channel Update Rate
Open Circuit Detection Time
Conversion Method
Accuracy vs. Temperature
Maximum Inaccuracy
Linearity Error (end to end)
Input Stability and Repeatability
Maximum Full Scale Calibration
Error
Offset Calibration Error
Maximum Crosstalk at DC,
50Hz and 60Hz
Recommended Fuse (external)
External Power Supply Required
Sales 800-633-0405
4
0–20 mA
13-bit
0–20 mA = 2.44 µA per count
(1LSB = 1 count)
0–8191 counts
Sinking, Single-ended (1 common)
±31mA
247Ω, ±0.5%, 1/4W Current Input
Low Pass, -3dB @ 120Hz
2.5 ms per channel
(does not include ladder scan time)
10ms
Zero reading within 100ms
Successive approximation
±75PPM / ºC maximum
0.5% of range
(including temperature drift)
±0.037% of range
Monotonic with no missing codes
±0.024% of range
±0.098% of range
±0.098% of range
±0.049% of range
Edison S500-32-R, 0.032 A fuse
24VDC (-20% / + 25%), 30mA
P1-04ADL-1 Analog Input
P1-04ADL-1
The P1-04ADL-1 Low Resolution Analog Input
Module provides four current sinking channels for
converting 0–20 mA analog signals to a digital value
of 0–8191 (13-bit) for use with the Productivity1000
system.
Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . 1
General Specifications . . . . . . . . . . . . . . . . . . . . . . 2
Terminal Block Specifications . . . . . . . . . . . . . . . . . 2
Wiring Diagram and Schematic . . . . . . . . . . . . . . . . 3
Module Installation Procedure . . . . . . . . . . . . . . . . . 4
24V
QR Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Wiring Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
I1+
Module Configuration . . . . . . . . . . . . . . . . . . . . . . . 5
I2+
Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Non-Linear Scaling . . . . . . . . . . . . . . . . . . . . . . . . . 6
I3+
Warning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
I4+
0V
COM
COM
COM
COM
0-20mA INPUT
Terminal Block sold separately, (see wiring options on page 5).
ANALOG
Warranty: Thirty-day money-back guarantee. Two-year limited
replacement (See www.productivity1000.com for details).
www.productivity1000.com
1000