Automationdirect.com Productivity 1000 P1-04ADL-1 Handbuch - Seite 3
Blättern Sie online oder laden Sie pdf Handbuch für E/A-Systeme Automationdirect.com Productivity 1000 P1-04ADL-1 herunter. Automationdirect.com Productivity 1000 P1-04ADL-1 8 Seiten. Analog input
P1-04ADL-1 Schematic
MODULE CIRCUITRY
24 VDC User
Supplied Power
-
+
24V
I1+
I2+
I3+
I4+
0V
COM
COM
COM
COM
Sales 800-633-0405
INTERNAL
ISOLATED ANALOG
CIRCUIT POWER
CH1 ADC
247
CH2 ADC
247
CH3 ADC
247
CH4 ADC
247
ISOLATED ANALOG
CIRCUIT COMMON
P1-04ADL-1 Wiring Diagram
Current Input Circuits
An Edison S500-32-R 0.032 A fast-acting
fuse is recommended for current loops.
–
2-Wire 4–20 mA
T ransmitte r
+
2-Wire Transmitter
+
+
3-Wire Current
Transmitter
–
3-Wire Transmitter
+
4-Wire 4–20 mA
Transmitter
–
User Supplied
AC or DC
Transmitter Power
4-Wire Transmitter
Note: Do not connect both ends of shield.
www.productivity1000.com
fuse
I+
.032 A
+
–
+24VDC User
Supplied Power
COM
fuse
I+
.032 A
+
–
+24VDC User
Supplied Power
COM
fuse
I+
.032 A
COM
3