With the control panel in the programming mode, enter the 7 digit serial
number that is on the label of the 5808LSTA. For confirmation, press the
test switch to send a transmission to the control panel.
See the control unit's installation instructions for further details.
SMOKE DETECTOR LIMITATIONS
• Smoke detectors will not sense a fire if the smoke does not reach the
sensor or if the air temperature does not reach 135° F. In order for a
smoke detector to sense smoke, it must be installed in the immediate vicin-
ity of the fire. In addition, smoke from fires in chimneys, in walls, on roofs,
in remote parts of the building, or on another level from where the smoke
detector is located, may not reach the smoke detector quickly enough for
occupants to escape unharmed. For this reason, installer shall install
smoke detectors on every level, in every sleeping area, and in every
bedroom of the household.
• Smoke detectors may not be heard. The alarm horn in this smoke detector
meets or exceeds current Underwriter's Laboratories standards. However, if
the smoke detector is not located in the same room as the occupant, or if
it is blocked by a closed door or normal noise, the alarm horn may not be
heard. In addition, sound sleepers, or persons who are under the influence of
drugs or alcohol may not hear the alarm or be able to react to it. Therefore,
locate this smoke detector, which has a sounder rated at 85 dB at 10
feet, on every level, in every sleeping area, and in every bedroom of the
household.
• In general, detectors may not always warn you about fires caused by
carelessness and safety hazards like smoking in bed, violent explosions,
escaping gas, improper storage of flammable materials, overloaded electri-
cal circuits, children playing with matches, or arson.
• Smoke detectors are not fool-proof. Like all electronic devices, smoke
detectors have limitations. No type of smoke detector can sense every
kind of fire every time. In addition, smoke from slow, smoldering fires
rises slowly and may not reach the smoke detector until actual flame
breaks out. This type of smoke may not reach the smoke detector in
time for occupants to escape unharmed.
• Smoke detectors are not a substitute for life or property insurance.
Though smoke detectors have been responsible for saving many lives, they
are not warranted or implied to protect lives or property in the event of a
fire.
• To keep your equipment in excellent working order, ongoing maintenance
is required per the manufacturer's recommendations and ULC and NFPA
standards. At a minimum, the requirements of Chapter 7 of NFPA 72, the
National Fire Alarm Code, shall be followed. A preventative maintenance
agreement should be arranged through the local manufacturer's representa-
tive. Though smoke detectors are designed for long life, they may fail at any
time. Any smoke detector, fire alarm equipment, or any component of that
system which fails shall be repaired or replaced as soon as possible.
Where to Install Smoke Detectors
Warning: As a minimum requirement, smoke detectors must be installed in
accordance with the National Fire Protection Agency (NFPA) Standard 72,
Chapter 5, which defines the standards for the National Fire Alarm Code
(National Fire Protection Association, Batterymarch Park, MA 02269-9101),
and CAN/ULC S524. In addition, observe all local and national building and
electrical codes.
Where Smoke Detectors Should NOT Be Installed
• In or near areas where combustion particles are normally present such
as kitchens; in garages where there are particles of combustion in vehicle
exhausts; near furnaces, hot water heaters, or gas space heaters. Install
detectors at least 20 feet (6 meters) away from kitchens and other areas
where combustion particles are normally present.
• On the ceiling in rooms next to kitchens where there is no transom
between the kitchen and these rooms. Instead, install the smoke detector on
an inside wall, furthest from the kitchen. Be sure not to install smoke detec-
tors within 4" of the ceiling or any corner or more than 6" from the ceiling.
• In damp or very humid areas, or next to bathrooms with showers. The
moisture in humid air can enter the sensing chamber as water vapor, then
cool and condense into droplets that cause a nuisance alarm. Install detec-
tors at least 5 feet (1.5 meters) away from bathrooms.
• In very cold or very hot rooms or areas. Operating temperature of the
smoke detector is 40°F to 100°F (4°C to 38°C).
• In dusty, dirty, or insect-infested areas. Dust and dirt can build up on the
detector's sensing chamber and make it overly sensitive, or can block open-
ings to the sensing chamber and keep the detector from sensing smoke.
• Near fresh air inlets or returns or excessively drafty areas. Air con-
AD300-00-00
ditioners, heaters, fans, and fresh air intakes and returns can drive smoke
away from smoke detectors, making the detectors less effective.
• In dead air spaces at the top of a peaked ceiling or wall/ceiling intersect.
Dead air may prevent smoke from reaching a detector.
• Near fluorescent light fixtures. Install detectors at least 10 feet
(3 meters) away from such light fixtures.
WHAT TO DO IN CASE OF FIRE
1. DON'T PANIC — escape may depend on clear thinking.
2. Get out of the house following the planned escape routes, if possible.
Do not stop to dress or to collect anything.
3. Open doors carefully only after feeling them to see if they are hot. If a
door is hot, do not open it— follow an alternate escape route.
4. Keep close to the floor — smoke and hot gases rise. Breathe through
a cloth (wet, if possible) and take short shallow breaths.
5. Keep doors and windows closed unless it is necessary to open them
for escape.
6. Meet at your meeting place after leaving your home.
7. Call the local fire department as soon as possible from outside
the home.
8. Never re-enter a burning building.
For more information about fire safety, contact your local fire department.
They can supply more detailed information about making your home as
free from fire hazards as possible and about planning for escape in case
of fire.
MOUNTING
First, determine the best location for the smoke detector; a location that
provides strong wireless transmission paths and proper smoke detec-
tion. A GOOD TRANSMISSION PATH MUST BE ESTABLISHED FROM
THE PROPOSED MOUNTING LOCATION BEFORE PERMANENTLY
INSTALLING THE DETECTOR. To check, perform the test described in
the TESTING TRANSMITTER SIGNAL section of this manual. To mount
the detector:
1. Once a suitable location has been determined, install the mounting
bracket on the ceiling or on the wall (if local ordinances permit). Use
the two screws and anchors provided.
2. Prior to mounting the detector to the mounting bracket, the system
must "enroll" the detector's ID. See the PROGRAMMING section for
the steps to follow.
3. Turn the detector in a clockwise direction in the mounting bracket until
it clicks into place.
4. Test the detector immediately after completing the installation (as
described in the TESTING section of this manual) and refer to the
control system's instructions for additional information concerning the
use of wireless smoke detectors.
TAMPER SLOT
(DEPRESS TAB TO
REMOVE DETECTOR)
Figure 2. Detector Mounting Bracket
Figure 3. Mount Detector Across Ceiling Panel Support
2
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO
ACTIVATE TAMPER-RESIST
FEATURE)
ALIGNMENT
ARROWS
A78-2333-06
I56-2249-00