Merlin CO2 Monitor 2800ppm
1
General information
The Merlin CO2 Monitor has a LED display to show the user a clear and precise reading of the CO2
level in the room also the traffic light colour system indicates the air quality in the area.
The Merlin CO2 Monitor can be used independently or can work in conjunction with one of our Merlin
gas control systems. If the CO2 reaches alarm level the Merlin CO2 Monitor would sound an audible
alarm to alert the user and also send a signal to the Merlin gas control system which will in turn close the
gas solenoid valve.
2
Installation
2.1
Mounting the CO2 Sensor The control panel is designed for surface mounting using 2
mounting screws. Removing the back plate gives access to the circuit board. Do not attempt
to remove the PCB.
2.2
Mains Supply A 100-240volt electrical supply should be supplied to the panel. This should be
externally fused at 3 Amps using a fused spur and should be connected to the terminals
marked "LN Power"
2.3
Alarm Relay This will switch over should the level of Co2 rise above 2800ppm, and
automatically switch back once the levels have dropped below 2750ppm.
2.4
Pre Alarm Relay This will switch over should the level of Co2 rise above 1500ppm, and
automatically switch back once the levels have dropped below 1450ppm.
2.5
Temperature Relay This will switch over should the sensor detect the temperature
above 86° Fahrenheit, and switch back once the temp drops back below 84° Fahrenheit.
2.6
0-10 Volt DC Output The voltage will increase / decrease depending on the ppm read out of
Co2 detected. 2V per 1000ppm.
2.7
Audible Alarm There is a dip switch on the circuit board to activate or de-activate the in-built
audible alarm. (On = on & 1 = Off). This will sound at 1500ppm if enabled.
Note: all low voltage connections should be made using a screened cable to avoid electrical interference.
3
Operation Instructions
How to turn the system on and off
3.1
1. To turn on the Merlin CO2 monitor you need to supply 100-240V into the "L & N POWER"
terminal, this will then illuminate the blue LCD screen and initiate a 60 second countdown. When
the countdown is complete the LCD screen will show the CO2 levels in the room.
2. To turn off the Merlin CO2 monitor you need to turn the power supply to the panel off or
disconnect the fuse spur.
Explanation of LED status
3.2
3.2.1
Low (Green) LED
Green - Good air quality, CO
3.2.2
Medium (Amber) LED
Yellow - Moderate air quality, 1000ppm> CO
3.2.3
High (Red) LED
Red - Poor air quality CO
Rev: 04 Date: 09-07-18
<1000ppm
2
< 1500ppm
2
>1500ppm
2
User & Installation Manual
3