Galvin Specialised CliniLever TCWMJ80PC Handbuch - Seite 3

Blättern Sie online oder laden Sie pdf Handbuch für Sanitärprodukt Galvin Specialised CliniLever TCWMJ80PC herunter. Galvin Specialised CliniLever TCWMJ80PC 4 Seiten. Healthcare tapware

3. Fit water temperature indicator
®
Once CliniLever
lever handle is secure, fit
the water temperature indicator.
Ensure the set is installed with hot and cold
in the correct location.
TROUBLESHOOTING
PROBLEM
Taps are dripping water
Water is leaking from spindle
Water is not flowing from tap
Spindle is difficult to turn
(jumper valve)
Handle is loose
Flange does not screw down
onto basin/sink surface
4. Testing
CAUSE
Jumper valves are worn or damaged
Ceramic discs are worn or damaged
Tap seat is damaged
O-ring on jumper valve spindle is
damaged or worn
Water is turned off
Aerator or flow regulator is blocked by
debris
Build up of scale on spindle, spindle
worn or o-ring has been damaged
Screw has come loose
Tap bodies are set too far out
Version 2, 18 July 2017, Page 3 of 4
Once temperature indicator is fitted, check the
operation of the unit and inspect for any leaks.
RECTIFICATION
Replace jumper valve
Remove and inspect SBA.
Remove debris and/or replace
SBA if damaged.
Refurbish tap seat using a
reseating tool.
Replace o-ring
Turn water on
Remove aerator and/or flow
regulator from tap and remove
debris. Install an inline strainer.
Remove jumper valve, clean and
regrease. Replace o-ring.
Complete SBA may need to be
replaced.
Tighten handle screw
Re-position tap bodies and breach
piece