Adey Mini 130 Installation und Instandhaltung - Seite 11
Blättern Sie online oder laden Sie pdf Installation und Instandhaltung für Water Pump Adey Mini 130 herunter. Adey Mini 130 17 Seiten. Digital pressurisation unit
Sets low system pressure alarm. Set in 0 . 0 5 bar increments
P4 Lo Alarm (4)
below the System pressure (2) - Differential pressure
see Fig . 18
(3) - 0 . 0 5 bar . Alarm auto resets when system pressure is
increased above alarm level
Sets number of pumps fitted to APU . 1 or 2 pumps . Factory
P5 Pump number
set to suit model .
Allows pump 1 or 2 to be forced to run for 15 seconds to
confirm operation.
P6 Pump test
Using buttons A or B to select pump 1 or 2, then press button
A or B again to run the pump .
P7 Info.
Displays software revision. No inputs .
6 .19 Pre-set values
The APU will be delivered with the following pre-set values:-
Set Pressure
2 bar
Differential
0 .2 bar
Hi Alarm
2 .5 bar
Lo Alarm
1 . 3 bar
6 .20 Hydraulic commissioning:
Ensure both inlet and outlet hydraulic connections are made and
z
watertight .
Turn on water supply to APU – Check for leakage and operation of fill
z
valve .
Allow the tank to fill and water level to stabilise . Adjust the float of the
z
fill valve to set the water level if needed .
Close isolation valve on the outlet of the APU .
z
Turn the electrical supply ON to the APU . The system pressure will be
z
displayed .
The APU will run briefly and then turn off after a pre-set run on time .
z
Due to the small size of the isolated system the APU will signal a Hi
pressure error and the red error light will illuminate on the front of the
APU, this is normal .
Open the isolation valve on the outlet of the APU and the APU will
z
run and start to top the system up .
6 .21 For further technical support: Phone the ADEY Customer Service team
on +44 (0) 1242 546717 . Our staff are trained to help and advise you over
the phone .
- 20 -
7 OPERATION
7 .11
Normal operation:
The 'Home' screen will display the status of the system pressure .
Fig . 21
A green 'Power on' light will be displayed on the front of the APU .
During normal operation the APU will monitor the system pressure and re-
pressurise the system if the system pressure drops below the system pressure
– differential pressure . See Fig . 18 .
Example: System pressure 2 bar, differential pressure 0 .5 bar, pump will start
to re-pressurise system at 1 .5 bar system pressure and stop at a system
pressure of 2 bar .
During the normal operation of a pressurised system, the system pressure
will fluctuate due to temperature changes causing expansion and contraction .
When setting the differential pressure for the Hi \ Lo alarms, please ensure
that the normal system pressure fluctuations are below the Hi pressure alarm
setting and above the differential pressure . If this is not done the APU will try
to compensate for the pressure change causing an over pressure within the
system or alarms being triggered .
7 .12 Error and alarm display:
The following errors are shown on the display:
Hi
Pressure monitored by the APU Mini is above the Hi alarm set pressure .
Display will flash between Hi and system pressure and red error light
will illuminate . Pumps will not run in this condition .
Lo
Pressure monitored by the APU Mini is below the Lo alarm set pressure .
Display will flash between Lo and system pressure and red error light will
illuminate . Pumps will run in this condition .
Er
The input signal from the pressure sensor is outside its normal range .
Display will flash Er and red error light will illuminate .
- 21 -