ADF Web HD67506 Benutzerhandbuch - Seite 15
Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Industrielle Ausrüstung ADF Web HD67506 herunter. ADF Web HD67506 18 Seiten.

Industrial Electronic Devices
The Bytes that composed the respons are these:
n="Number of Point *2" if Type of Data is 3,4 or n="(Number of Point+7)/8" if Type of Data is 1,2
The "Status of operation" (Byte Number 1) can have these values:
0xFF: Ok;
0xFE: Different from Read;
0xFD: Reading but function different from 1,2,3,4;
0xFB: The slave interrogated hasn't replied in the TimeOut time;
0xFA: The reply CRC is wrong;
0xF9: Returned function is different from the one requested;
0xF8: Number of byte different from 7;
0x03: Illegal data value, the value referenced in the data field is not allowable in the addressed slave location;
0x02: Illegal data address, the address referenced in the data field is not an allowable address for the addressed slave device;
0x01: Illegal function, the message function received is not an allowable action for the addressed slave.
Example:
1) We want to read two points with the following features:
Type of Data: Holding Register; Device Address: 5; Start Address: 0x0115; Number of Point: 2.
So the string of hexadecimal numbers is:
REQ:[01][03][05][01][15][00][02]
The slave respond with two data: the first is 0x1122 and the second is 0x3344.
RES:[FF][11][22][33][44]
ADFweb.com S.r.l.
Byte Number
Description
1
Status of operation
2÷n+1
Data
User Manual Modbus Master / Ethernet
Document code: MN67506_ENG
Revision 1.012
Page 15 of 18