The Bytes that composed the respons are these:
n="Number of Point *2" if Type of Data is 3,4 or n="(Number of Point+7)/8" if Type of Data is 1,2
The "Status of operation" (Byte Number 1) can have these values:
0xFF: Ok;
0xFE: Different from Read;
0xFD: Reading but function different from 1,2,3,4;
0xFB: The slave interrogated hasn't replied in the TimeOut time;
0xFA: The reply CRC is wrong;
0xF9: Returned function is different from the one requested;
0xF8: Number of byte different from 7;
0x03: Illegal data value, the value referenced in the data field is not allowable in the addressed slave location;
0x02: Illegal data address, the address referenced in the data field is not an allowable address for the addressed slave device;
0x01: Illegal function, the message function received is not an allowable action for the addressed slave.
Example:
1) We want to read two points with the following features:
Type of Data: Holding Register; Device Address: 5; Start Address: 0x0115; Number of Point: 2.
So the string of hexadecimal numbers is:
REQ:[01][03][05][01][15][00][02]
The slave respond with two data: the first is 0x1122 and the second is 0x3344.
RES:[FF][11][22][33][44]
ADFweb.com S.r.l.
Byte Number
Description
1
Status of operation
2÷n+1
Data
User Manual Modbus Master / Ethernet
Document code: MN67506_ENG
Revision 1.012