Dell Force10 S60 Series Schnellstart-Handbuch - Seite 14

Blättern Sie online oder laden Sie pdf Schnellstart-Handbuch für Schalter Dell Force10 S60 Series herunter. Dell Force10 S60 Series 29 Seiten.
Auch für Dell Force10 S60 Series: Handbuch (45 seiten)

Dell Force10 S60 Series Schnellstart-Handbuch
NOTE: Both slots must have operating fan units to run the system. If a module is
not installed in each slot (either as part of the PSU or as an independent fan
module), the system will shut down in 1 minute.
The S55 and the S60 both support two airflow direction options. Only a single
direction can be used in a chassis; do not mix fan flow types in a chassis. The
system will shutdown in 1 minute, if the airflow directions are mismatched.
Normal is airflow from I/O panel to power supply
Reversed is airflow from power supply to I/O panel
There are environmental factors that could decrease the amount of time required
between air filter replacements. Check these environmental factors regularly.
Any unusual environmental circumstance at the site that causes an increase in
temperature and/or particulate matter in the air might affect performance (for
example, new equipment installation).

Specifications

Chassis Physical Design

Parameter
Height
Width
Depth
Chassis weight with
factory-installed
components
Rack clearance required Front: 5-inches (12.7 cm)
Thermal dissipation
Power Consumption
12
Installing the Hardware
S55 Specifications
1.73 inches (4.4 cm)
17.32 inches (44.0 cm)
18.74 inches (47.6cm)
14.41 pounds (approx.) (6.54
kg)
Rear: 5-inches (12.7 cm)
461 BTU/hr (135W)
115 Watts (nominal)
135 Watts (maximum)
S60 Specifications
1.7 inches (4.3 cm)
17.32 inches (44.0 cm)
16.73 inches (42.5cm)
14.39 pounds (approx.) (6.54
kg)
Front: 5-inches (12.7 cm)
Rear: 5-inches (12.7 cm)
597 BTU/hr
175 Watts (nominal)
225 Watts (maximum)