Maintenance
Motor maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be limited to exterior
surfaces only. Removing dust buildup on motor housing ensures proper motor cooling. Greasing of motors is only intended
when fittings are provided. Many fractional motors are permanently lubricated and should not be lubricated after installation.
Motors supplied with grease fittings should be greased in accordance with manufacturers' recommendations. With motor
temperatures under 104ºF (40ºC), the grease should be replaced after 2000 hours of running time as a general rule.
Wheels require very little attention when moving clean air. Occasionally, oil and dust may accumulate causing imbalance.
When this occurs, the wheel and housing should be cleaned to ensure smooth and safe operation.
All fasteners should be checked for tightness each time maintenance checks are performed prior to restarting unit.
A proper maintenance program will help these units deliver years of dependable service.

Troubleshooting

PRObLEM
REDUCED
AIRfLOW
ExCESSIvE
NOISE OR
vIbRATION
NOTE: Before taking any corrective action, make certain unit is not capable of operation during repairs.
Replacement
Parts
*VERTICAL
NOTE
Each fan bears a manufacturer's nameplate with model number and serial number embossed. This information
will assist the local Accurex representative and the factory in providing service and replacement parts.
Accurex warrants this equipment to be free from defects in
material and workmanship for a period of one year from the date of
purchase. Any units or parts which prove to be defective during the
warranty period will be replaced at our option when returned to our
factory, transportation prepaid. Motors are warranted by the motor
manufacturer for a period of one year. Should motors furnished by
Accurex prove defective during this period, they should be returned
to the nearest authorized motor service station. Accurex will not be
responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Accurex
reserves the right to change specifications without notice.
CAUSE
System resistance too high.
Unit running backwards.
Excessive dirt buildup on wheel.
Improper wheel alignment.
Wheel improperly aligned and rubbing.
Foreign objects in wheel or housing.
Unbalance of wheel caused by excessive
dirt and grease buildup.
HOOD
BIRDGUARD
CONDUIT
CHASE
SUPPORTS
*DRAIN
TROUGH
*CURB CAP /
VENTURI
Warranty
CORRECTIvE ACTION
Check system: Proper operation of
backdraft or control dampers,
obstruction in ductwork, etc.
Correct as shown in Fig. 2.
Clean wheel.
See Fig. 1 and Pre-Starting Checks.
See Fig. 1 and Pre-Starting Checks.
Remove objects, check for damage.
Remove buildup.
MOTOR
SHOCK
MOUNTS
BREATHER
TUBE
*WINDBAND
*For replacement, the windband,
vertical supports, drain trough
WHEEL
and curb cap/venturi come as one
complete assembly.