8. Mounting

6

8.1 Actuator Check

- Is the actuator filled with the appropriate oil type?
- Is enough oil in the actuator?
- Did you fasten the separately delivered vent screw in the highest bore (depending
on the mounting orientation)?

8.2 Mounting Orientation

See table 2 for permissible mounting orientations. To facilitate mounting and mainte-
nance, however, it is recommended to use orientation IMB 3.

8.3 Mounting Instructions

- Make sure that the actuator is accessible from all sides to ensure convenient hand-
wheel operation, electrical connection, and replacement of assemblies.
- Avoid direct exposure to rain, snow and other environmental influences. Select the
mounting site accordingly.
- Exclusively mount the actuator on a rigid, non-vibrating support to avoid relative
motion between the actuator and the valve.
- When mounting the actuator close to heat sources use an insulating layer or shield-
ing.

8.4 Mounting the Actuator to the Valve

8.4.1 Preparing the Equipment
- Make sure that the shaft and lever bore surface are clean and free of grease.
- Determine the length of the stay tube (not included in the scope of delivery).
- Move the valve to the "CLOSED" position.
- Drive the actuator close to the corresponding end position. Use the handwheel for
the last few mm. Observe the permissible angle.
- Spacing "L" minus 300 mm gives the required length of the link tube.
- Drill a cone bore into the valve lever for mounting the second ball-and-socket joint,
as seen in Figure 4.
- Insert the ball-and-socket joint, secure with crown nut and split-pin.
- Remove the welding bushings and weld them to the stay tube (C 15 to DIN 17210)
- Insert the link rod between the two ball-and-socket joints and screw it in.
- If required adjust "L" by turning the link rod.
- When all adjustment steps are finished, fasten the counter nuts.
8.4.2 Adjusting the Stops in Dependence of the Travel
- Move the output lever / valve to the position requiring fine adjustment.
- Put the stop onto the toothing as close to the output lever as possible and fasten
with screws.
- Move the output lever towards the stop using the handwheel; turn the coupling rod
for fine adjustment.
- Fasten the counter nuts.
- Fasten the stop in the other mounting orientation close to the end position, depend-
ing on the toothing.
8.4.3 Adjusting the Stops in Dependence of the Torque
- First proceed as described in section 8.4.2.
- Prior to re-fastening the counter nuts lock the handwheel and turn the counter nut
until a pretension occurs in the valve's closed position.
- Fasten the counter nuts