ABB RHD8000 Series Anleitung Handbuch - Seite 6
Blättern Sie online oder laden Sie pdf Anleitung Handbuch für Controller ABB RHD8000 Series herunter. ABB RHD8000 Series 17 Seiten. Electrical part turn actuators for continuous modulating control (contrac)
8. Mounting
6
8.1 Actuator Check
- Is the actuator filled with the appropriate oil type?
- Is enough oil in the actuator?
- Did you fasten the separately delivered vent screw in the highest bore (depending
on the mounting orientation)?
8.2 Mounting Orientation
See table 2 for permissible mounting orientations. To facilitate mounting and mainte-
nance, however, it is recommended to use orientation IMB 3.
8.3 Mounting Instructions
- Make sure that the actuator is accessible from all sides to ensure convenient hand-
wheel operation, electrical connection, and replacement of assemblies.
- Avoid direct exposure to rain, snow and other environmental influences. Select the
mounting site accordingly.
- Exclusively mount the actuator on a rigid, non-vibrating support to avoid relative
motion between the actuator and the valve.
- When mounting the actuator close to heat sources use an insulating layer or shield-
ing.
8.4 Mounting the Actuator to the Valve
8.4.1 Preparing the Equipment
- Make sure that the shaft and lever bore surface are clean and free of grease.
- Determine the length of the stay tube (not included in the scope of delivery).
- Move the valve to the "CLOSED" position.
- Drive the actuator close to the corresponding end position. Use the handwheel for
the last few mm. Observe the permissible angle.
- Spacing "L" minus 300 mm gives the required length of the link tube.
- Drill a cone bore into the valve lever for mounting the second ball-and-socket joint,
as seen in Figure 4.
- Insert the ball-and-socket joint, secure with crown nut and split-pin.
- Remove the welding bushings and weld them to the stay tube (C 15 to DIN 17210)
- Insert the link rod between the two ball-and-socket joints and screw it in.
- If required adjust "L" by turning the link rod.
- When all adjustment steps are finished, fasten the counter nuts.
8.4.2 Adjusting the Stops in Dependence of the Travel
- Move the output lever / valve to the position requiring fine adjustment.
- Put the stop onto the toothing as close to the output lever as possible and fasten
with screws.
- Move the output lever towards the stop using the handwheel; turn the coupling rod
for fine adjustment.
- Fasten the counter nuts.
- Fasten the stop in the other mounting orientation close to the end position, depend-
ing on the toothing.
8.4.3 Adjusting the Stops in Dependence of the Torque
- First proceed as described in section 8.4.2.
- Prior to re-fastening the counter nuts lock the handwheel and turn the counter nut
until a pretension occurs in the valve's closed position.
- Fasten the counter nuts