INSTALLATION INSTRUCTIONS
CAUTION
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in
improper product operation.
Do not bury more than 36" (1m) of line set under-
ground. Refrigerant may migrate to cooler buried
section during extended periods of unit shut−
down, causing refrigerant slugging and possible
compressor damage at start−up.
If ANY section of the line set is buried under-
ground, provide a minimum 6" (152mm) vertical
rise at the service valve.
D. OUTDOOR UNIT HIGHER THAN INDOOR UNIT
Proper oil return to the compressor should be maintained
with suction gas velocity. If velocities drop below 1500 fpm
(feet per minute), oil return will be decreased. To maintain
suction gas velocity, do not upsize vertical suction risers.
E. LIQUID LINE FILTER−DRIER
NOTE:
It is recommended that an appropriate
filter−drier be installed in the liquid line.
Leave the plugs in the tube ends until the filter−drier is
installed. The optimal location for the filter−drier is close
to the indoor coil. Install the filter−drier with the arrow
pointing towards the indoor coil. Refer to Figure 6.
Liquid Line Filter−Drier
Figure 6
Installed at Indoor Coil
Filter−Drier
(arrow points towards indoor coil)
421 01 5301 02
F. SERVICE VALVES
Service valves are closed and tube stubs are plugged
from the factory. Outdoor units are shipped with a
refrigerant charge sealed in the unit. Leave the service
valves closed until all other refrigerant system work is
complete or the charge will be lost. Leave the plugs in
place until line set tubing is ready to be inserted.
Service valve bodies are brass and tube stubs are
copper.
G. BRAZING CONNECTIONS
!
FIRE HAZARD
Failure to remove refrigerant and oil charge be-
fore brazing could result in personal injury, death,
and/or property damage.
Refrigerant and oil mixture could ignite and burn
as it escapes and contacts brazing torch. Make
sure the refrigerant charge is properly removed
from both the high and low sides of the system be-
fore brazing any component or lines.
Clean line set tube ends with emery cloth or steel brush.
Remove any grit or debris.
Insert line set tube ends into service valve tube stubs.
Apply heat absorbing paste or heat sink product between
service valve and joint. Wrap service valves with a heat
sinking material such as a wet cloth.
Braze joints using a Sil−Fos or Phos−copper alloy.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in prod-
uct damage.
Braze with Sil−Fos or Phos−copper alloy on cop-
per−to−copper joints and wrap a wet cloth around
rear of fitting to prevent damage to TXV.
H. EVACUATING LINE SET AND INDOOR COIL
The unit is shipped with a factory refrigerant charge. The
liquid line and suction line service valves have been
closed after final testing at the factory. Do not disturb
these valves until the line set and indoor coil have been
evacuated and leak checked, or the charge in the unit
may be lost.
NOTE: Do not use any portion of the factory charge for
purging or leak testing. The factory charge is for filling the
system only after a complete evacuation and leak check
has been performed.
!
PRODUCT DAMAGE HAZARD
Failure to follow this caution may result in prod-
uct damage.
38−11−84
Never use the outdoor unit compressor as a vacu-
um pump. Doing so may damage the compressor.
Specifications subject to change without notice.
R−410A Split System Air Conditioner
WARNING
CAUTION
CAUTION
7