Acuity Controls ECLYPSE A1000 Installationshandbuch - Seite 4
Blättern Sie online oder laden Sie pdf Installationshandbuch für Relais Acuity Controls ECLYPSE A1000 herunter. Acuity Controls ECLYPSE A1000 10 Seiten. Asset tracking
Auch für Acuity Controls ECLYPSE A1000: Installationshandbuch (14 seiten)
1.0 - Introduction
1.4 General Wiring Recommendations
Any type of modification to any Acuity product will void the
product's warranty.
•
All wiring must comply with electrical wiring
diagrams as well as national and local electrical
codes.
•
To connect the wiring to a device, use the
terminal connectors. Use a small flat screwdriver to
tighten the terminal connector screws once the wires
have been inserted (strip length: 0.25'' (6 mm),
tightening torque 0.5 Nm).
•
Keep wiring separate according to their function
and purpose to avoid any ambient noise transmissi-
on to other wires. Use strapping to keep these wires
separated. For example, keep power, hazardous
voltage, SELV, network, and input wiring separate
from each other.
For the Power Supply module: When connecting one
wire to a controller's terminal block clamping cage
(pole), the wire must be between 18 and 14 gauge
(0.82 and 2.1mm
cross-sectional area). When
2
connecting two wires to a controller's terminal block
clamping cage, both wires must be the same thick-
ness, must be between 18 and 16 gauge (0.82 and
1.3mm
cross-sectional area), and must be the same
2
type (solid or stranded). Twist the wires together and
insert then into the controller's terminal block
clamping cage. For any other wiring combination
(mixed wire thickness, mixed solid and stranded
conductors, more than three wires, wire thickness is
out of range), twist the wires together and use a wire
nut and a pig tail to connect to the controller's
terminal block connector as shown below.
Wire Nuts
Pigtails
Terminal Block
Connector
Controller
Figure 1: Using a Wire Nut and Pigtail to Wire the Controller
•
Keep all wires away from high speed data transmissi-
on cables (for example, Ethernet, etc.).
•
Keep input and output wiring in conduits, trays or
close to the building frame if possible.
•
Use the screws, wall anchors, and wire nuts included
for wall mounting and wiring
Acuity Brands | One Lithonia Way Conyers, GA 30012 Phone: 800.535.2465 www.acuitycontrols.com © 2017-2019 Acuity Brands Lighting, Inc. All rights reserved. 03/29/19
Wire Connections
.
1.5 Module Enclosure Dimensions
3.57" 90.67
Inter-Connection Gap: 0.01" 0.40
4.74" 120.31
5.13" 130.29
0.39" 9.98
0.06" 1.44
Front
3.33" 84.47
Figure 2: Server Module
DC Power
Source
Fuse: 4A
Max. Fast
Acting
Figure 3: PS24 Power Supply
Figure 4: Side view - all modules
0.4"
1.09
Back
AC Power
Source
(Mains)
Fuse: 4A
Max. Fast
Acting
2.31" 58.56
A1000AT_IG_10_EN
0.83
21.08
3.18" 80.82
0.73
18.54
Inches Millimeters
4 of 10