ABB FENA-11 Kurzanleitung für Installation und Inbetriebnahme - Seite 2

Blättern Sie online oder laden Sie pdf Kurzanleitung für Installation und Inbetriebnahme für Kontrolleinheit ABB FENA-11 herunter. ABB FENA-11 2 Seiten. Ethernet adapter module, options for drives

ABB FENA-11 Kurzanleitung für Installation und Inbetriebnahme
2
Start-up
When the module is connected to the drive, the drive control program sets the applicable parameters. See
the appropriate drive firmware manual.
Basic parameter settings
Index
Name
20.01
Ext1 commands
22.11
Speed ref1 source
28.11
Frequency ref1 source
50.01
FBA A enable
50.02
FBA A comm loss func
Protocol-specific parameter settings
PROFINET IO
Index
Name
51.02
Protocol/Profile
51.04
IP configuration
51.05...08
IP address
51.09
Subnet CIDR
52.01
FBA A data in1
52.02
FBA A data in2
53.01
FBA A data out1
53.02
FBA A data out2
To take the settings into use, validate and refresh the parameters with parameter 51.27 FBA par refresh.
Connectivity configuration
To access the configuration web page:
1. Open a web browser and type the IP address of the adapter module in the address field.
2. Log in with a user name (admin) and a password (The last six digits of the MAC address of the adapter
module, in upper case letters, without hyphens. Eg, if MAC ID is 00-1C-01-00-2F-73, the password is
002F73).
Further information
See the latest version of FENA-01/-
11/-21 Ethernet adapter module user's
manual (3AUA0000093568 [English])
in ABB library
www.abb.com/drives/documents
abb.com/drives
© Copyright 2019 ABB. All rights reserved.
Specifications subject to change without notice.
Value
Fieldbus A
FBA A ref 1
FBA A ref 1
Enable (or select the option slot in which the module is installed).
This activates the communication module. The HOST LED becomes green.
Fault
Value
PNIO ABB Pro
Static IP
0.0.0.0
0
SW 16bit
Act 16bit
CW 16bit
Ref1 16bit
FENA-01/-11/-21
manual
For more information on ABB fieldbus
options and protocols, see the field-
bus communications web page
new.abb.com/drives/connectivity/field-
bus-connectivity
Ethernet/IP
Index
Name
51.02
Protocol/Profile
51.04
IP configuration
51.05...08
IP address
51.09
Subnet CIDR
51.23
Speed scale
Modbus/TCP
Index
Name
51.02
Protocol/Profile
51.04
IP configuration
51.05...08
IP address
51.09
Subnet CIDR
Value
EIP AC/DC
Set the IP address
according your network
configuration.
128
Value
Modbus/TCP
Set the IP address
according your network
configuration.
Fieldbus communications