DISCOVER LYNK Edge Card Victron Benutzerhandbuch - Seite 5

Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Kamera-Zubehör DISCOVER LYNK Edge Card Victron herunter. DISCOVER LYNK Edge Card Victron 9 Seiten. Lithium ion battery

4 Configuring Victron Products

4.1 VE.Configure Settings

You will need the latest firmware on all connected devices. This section presumes familiarity with VEConfigure software.
These settings are for an off-grid application. These parameters once set will become the default values used if
communication with the AES battery is interrupted for some reason. During normal operation the charge characteristics are
governed automatically by the CCGX via DVCC, with instructions from the connected AES battery. However it is necessary
to set the discharging parameters for DC input low shut-down found under the Inverter Tab. After setting the parameters,
'send' all parameters to the inverter and CCGX. Restart the CCGX after completion.
Overruled by remote
Enable battery monitor
SoC when Bulk finished
Total battery capacity (per battery installed)
Charge efficiency
DC input low shut-down
DC Input low restart
DC input low pre-alarm
Enable AES
(6)
Enable charger
Battery Type
(2)
Lithium batteries
Charge curve
(2)
Absorption voltage
Float voltage
(2)
Charge current per battery installed
(Recommended < Maximum)
Repeated absorption time
Repeated absorption interval
Absorption time
(1) Enabled is recommended.
(2) Precautionary setting as they are ignored during normal operation and communication with AES Battery.
(3) The lowest operating voltage allowed, increase voltage as required.
(4) Restart voltage after DC input low shut-down, recommended to be set to the minimum value (minimum varies according to
the DC Input low shut-down value).
(5) 51.0 V value (approximately 15% SoC) will trigger low battery warning, increase or decrease as preferred.
(6) 'Enable AES' has no relation to the AES Battery, refer to Victron manuals for information on setting and function.
(7) The recommended minimum is 1.0 hour. A longer period of time may be required to compensate for multiple batteries to
achieve a smooth completion of charge.
Confirm the Float Voltage after completing the installation of any Victron
'Assistants', and if necessary reset the Float Voltage back to 26.8 V / 53.6 V.
5
General Tab
(1)
(2)
(2)
Inverter Tab
(3)
(4)
(5)
Charger Tab
(2)
(2)
(2) (7)
(2)
(2) (7)
44-24-2800
Enable
Enable
95%
installed x 110 Ah
95%
44-24-2800
Copper compression lug
24.0 V
26.0 V
Shrink-wrap to
25.5 V
color-code the cable
Disable
Terminal surface
44-24-2800
Enable
Blank
Enable
Select: Fixed
27.2 V
26.8 V
installed x
(78 A < 110 A)
1.0 < 3.0 Hr
7.0 Days
1.0 < 3.0 Hr
▲ NOTE
42-48-6650
Enable
Enable
95%
installed x 130 Ah
95%
42-48-6650
M8" bolt (supplied with battery)
48.0 V
Lock washer (supplied with battery)
52.0 V
Flat washer (supplied with battery)
51.0 V
Battery cable lug
Disable
Ensure nothing is between
the terminal surface and the
battery cable lug
42-48-6650
Enable
Blank
Enable
Select: Fixed
54.4 V
53.6 V
installed x
(92 A < 130 A)
1.0 < 3.0 Hr
7.0 Days
1.0 < 3.0 Hr
discoverbattery.com