The following is intended to provide the basic instructions for operation and maintenance.
Read and understand these operation instructions before use.

PRODUCT RATINGS

Flow:
1-1/2": 15-350 gpm at 100 psi
2-1/2": 350-500 gpm at 100 psi
Maximum Pressure: 200 psi/14 bar
Minimum Voltage at motor: 12 Volt Motor: 10 Volts
Maximum Motor Current Draw:
Noise Emission: 86 dB @1m with maximum flow

PRODUCT WARNINGS

Charge all lines slowly to facilitate a controlled water pressure build-up during start-up.
Open and close slowly. Rapid opening will produce a sudden thrust. Rapid opening and
closing can cause water hammer. Have your monitor properly supported to control the
reaction force created by the stream.
At pressures below that indicated on the label, the nozzle will have reduced flow and
reach. Be sure you have enough flow and pressure for the situation (See IFSTA and
NFPA manuals for guidelines).
Ensure the nozzle is aimed in a direction that is safe, prior to flowing.
Do not use the nozzle as a forcible entry tool. Doing so may damage it or make it
inoperable.
Ensure the thread on the nozzle swivel is matched to the thread on the monitor.
If any tags or bands on the nozzle are worn or damaged and cannot be easily read, they
should be replaced.
For use with fresh water or standard firefighting foams only. Not recommended for use
with salt water. After use with foam or salt water, flush with fresh water.
For firefighting use only.
Do not over tighten the nozzle onto the monitor.
The nozzle is configured for optimum performance. Do not alter in any manner.
PHONE: 800.228.1161 | WEBSITE: www.akronbrass.com
Sheet: 119695
STYLE 3293 FIREFOX
OPERATING INSTRUCTIONS
24 Volt Motor: 20 Volts
12 Volt Motor: 3 amps
24 Volt Motor: 1.5 amps
Indicates a hazardous situation which, if not avoided, WILL result in death or serious
injury.
Indicates a hazardous situation which, if not avoided, COULD result in death or serious
injury.
Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury.
Addresses practices not related to personal injury.
Revision 09/2022
NOZZLES