a. Expect an open circuit (∞Ω) between Terminals
C and NO (see Fig. 10). The ALARM CUTOFF
LEDs should not be lit.
NOTE: Under normal conditions, that is, with
power on and fuse installed, expect an open
circuit (∞Ω) between Terminals C and NO on
the rear of the demarcation panel.
NOTE: If a fuse, expect continuity (0Ω) between
Terminals C and NO.
23. Wire-wrap alarm pins with solid #26 to #22 AWG.
24. Enable loads and verify the normal operating
conditions outlined in the preceding Notes.

1.5 Replacing Alarm Cards

The alarm card is held in place by two captive
thumbscrews on the front of the alarm card panel.
To remove and replace an alarm card, unscrew the
thumbscrews and pull out the card.
When replacing an alarm card, make sure the edge
connector on the far end of the assembly docks
securely into the connector inside the panel.
High-Current
Demarcation Panel

Fig. 10: Alarm relay terminals on rear of panel

Fig. 11: Replacing the alarm card