Atkinson Electronics A0217 Manual - Página 2
Navegue en línea o descargue pdf Manual para Unidad de control Atkinson Electronics A0217. Atkinson Electronics A0217 16 páginas. Generator start control module
Table of Contents
.......................................................................
Specifications
..................................................................
...................................................
.................................................
Electric Start Generators without Control Box
Low Speed Generators with Safeties
........................................................
.................................................
......................................................
Not Included But......
48 Volt inverter systems
Require isolation relay
A0365
Code Version Update Changes
GSCM Rev. C set up adjustments is now accomplished
with three push buttons: Change/ store, menu up and
menu down.
GSCM Rev C-4.5HC has all adjustments hard coded with
set up mode disabled.
GSCM Rev C-5.13HC added a stop command after each
starting attempt to ensure generator is not already
running before trying to start a second or third time.
www.atkinsonelectronics.com
800.261.3602
........ .......................................
.........................................
.....................
............................
........................
........................................
...........................................
.......................
........
........................
................
...................
.............
Features & Applications
Automatic starting, load transfer and shutdown
3
for gas and diesel generators.
3
Off grid generators
Automatic adjustable voltage set points for
4
generator battery charging applications,
5
0-60VDC.
6
Works with 12, 24 or 48V battery systems.
7
Provides fault shutdown for low oil pressure, high
7
temperature and under-speed or over-speed
conditions.
8
All sequences have adjustable time periods.
9
30 day exercise with or without load, battery
9
equalize function available.
10
Relay driver for emergency shutdown and 30 day
11
exercise remote indication.
12 hour maximum runtime (with override) for
12
automatic starting applications.
12
Totally sealed for harsh environment operation.
13
13
Fully customize your needs for
14
start/stop generator operations.
14
15
16
Description
The GSCM is a micro-processor based generator starting
controller. It receives either automatic or manual start
commands to start a generator, disconnect the starter
when a minimum generator frequency output is
measured and monitors the generator operation,
shutting it down if one of several fault conditions are
detected.
LEDs are flashed to indicate the cause of the shutdown.
Manually resetting, the GSCM removes the lockout and
allows the generator to restart if called.
2
Circuit Board Division
Revised 09/18