17
08/14, fw. ver. V1.2, V1.3
Maximum fan speed
Output control
Note: Max. 3 outputs can be active at the same
time.
Inverted valve outputs
Fan control
Fan enable in Cooling mode
Fan enable in Heating mode
Not used
Not used
Minimum time previous fan stage upward
Integral time (I-part) PI regulator for fan control
Protect mode ON delay time via digital input
Fan ON delay time in AUTO mode
Return to factory defaults
0: Off / 1: Stage I / 2: Stage II / 3: Stage III
Bit value:
0: Output controlled with internal r. controller
1: Output directly controlled via Modbus
communication
Bit definition:
Bit 0: DO1 - output Cooling valve
Bit 1: DO2 - output Heating valve
Bit 2: DO3 - output Fan Stage I
Bit 3: DO4 - output Fan Stage II
Bit 4: DO5 - output Fan Stage III
Bit 5 - bit7: Not used
Bit value:
0: Normal output N.O.
1: Inverted output N.C.
Bit definition:
Bit 0: DO1 - output Cooling valve
Bit 1: DO2 - output Heating valve
Bit 2 - bit7: Not used
0: In fan Manual mode fan is active also in case
of inactive Cooling/Heating valve / 1: Fan can be
active only in case of active Cooling/Heating valve
0: Disabled / 1: Enabled
0: Disabled / 1: Enabled
0~9990 sec.
0~9990 sec.
0~600 sec.
0~9990 sec.
1: Reset to factory defaults