Wireless System Layout Hints:
Avoid locating transmitters and receivers on the same wall.
Avoid locating transmitters and receivers where the telegrams must penetrate walls at acute
angles. This increases the material the telegram must pass through reducing the signal
power.
Avoid large metal obstructions as they create radio shadows. Place receivers in alternate
locations to avoid the shadow or use repeaters to go around the obstacle.
Do not locate receivers close to other high frequency transmitters. Leave at least 3' (1 m)
between the receiver and any other source of interference including, ballasts, LED drivers,
computers, video equipment, Wi-Fi/LAN routers, GSM modems and monitors. Transmitters
are not affected by these sources of interference.

10. Product Specifications

Sensors
Carbon Dioxide
Technology: Ultra Low Power, LED based NDIR
Measurement Range: 0-2000 ppm
Accuracy: ± 50ppm
Altitude/Pressure Compensation: Built-in correction
Self-Calibration: Automatic Background Calibration
Resolution: 1 data byte (0-200 decimal), 10 ppm
Temperature
Range: 0ºC to 51ºC (32ºF to 124ºF)
Accuracy: ± 0.3ºC (± 0.5ºF)
Resolution: 1 data byte (0-255 decimal), 0.2ºC (0.36ºF)
Relative Humidity
Range: 0% to 100% RH
Accuracy: ±3% RH...10-90%, ±7%... 0-10%, 90-100%
Resolution: 1 data byte (0-200 decimal), 0.5%
Power Supply
Type: Integrated Solar Panel
Operational Light Levels: 50 lux
Minimum Charge Time before Operation: 10 min @ 200 lux
Charging Light Level: 200 lux
Maintain Operating Life Level: 200 lux for 6 hours
Maximum Charge Time: 16 hours @ 200 lux
Operating Life From Full Charge: 72 hrs @ 0.0 lux
Battery: for backup, start assist & test mode. Use high quality CR2032 coin cell (not included).
Typically will provide 5 year operating life in zero light conditions.
General
Weight: 115 g, (4 oz)
Mounting: screws or double sided tape (not included)
Listing: FCC Part15.231- Remote control transmitter,
Industry Canada RSS-210, RoHS compliant.

11. AirTest Contact Information

AirTest Technologies Inc.
1520 Cliveden Ave, Unit 9, Delta BC Canada V3M 6J8
www.AirTest.com
P: 604 517-3888, TF: 888 855-8880, F: 604 517-3888