LOOP = 0: By default, program looping is enabled. To disable program looping,
change LOOP to 0.
RUN = 3: By default, this controller is under single step mode. To use ramp soak
feature, set RUN to 3.
5. Wiring and programming example: powder coating/heat treatment oven
An oven needs to heat up to 375° F from ambient in 5 minutes. Then hold the
temperature for 20 minutes. After that, pull in the AL2 relay for 2 minutes. If the
temperature is higher than 450° F, trigger the AL1 relay. This application needs
a controller, a relay/SSR, a thermocouple and a two buzzers with a 12V DC
power source.
a. Wiring
Alarm1
Alarm2
12V
DC
1
13
14
2
SYL-
3
5352PA
+
4
-
5
10
TC
SYL-5352PA with Solid State Relay solution
Alarm1
Alarm2
12V
DC
1
13
14
2
3
SYL-5342PA
+
4
-
5
10
TC
SYL-5342PA with 40A contactor solution
b. Parameter setting and program
SSb = 5. Safety start band is set to 5 degree.
LOOP = 0. Program automatically looping is disabled.
ALP = 1. Alarm 1 is set to absolute high alarm.
AL1 = 450. Alarm 1 will be activated when reading temperature is over 450
AL2 = 120. Program ending alarm is set to 120s. Once all the steps have been
executed, alarm 2 will be activated for 120s.
T = 2 or 20. Set cycle time to 2s for SYL-5352PA, and set 20s for SYL-5342PA.
The program:
r01 = 2000, t01 = 0, C01 = 80. Initial step. r01 must be 2000. C01(80F) is ambient
temperature.
r02 = 5, t02 = 20, C02 = 375. Ramp up from 80 to 375 in 5 minutes, then soak
at 375 for 20 minutes.
r03 = 0, t03 = 0, C03 = 0. End of the program. Change all three parameters to 0.
Quick explanation: Cxx is end temperature of that step. rxx is the ramp step timer,
txx is the soak step timer. Every step, controller will run ramp up step at first,
then run soak step.
6. Windows Communication software notes:
2020.10
Heater
6
7
+
SSR
8
9
Heater
6
Contactor
7
8
9
1). Default login password is: admin
2). After you login, for first timer user, please click "Auto Select" on the right top of the
screen. Click "Detect" button on the right, then this software will automatically scan your
connected PID controller. Once finished, you will see SYL-53X2P-S is detected (if you PID
L1
model is SYL-5342P-S/SYL-5342PA/SYL-5352P-S/SYL-5352PA). Then click "Apply"
L2
button. If your software cannot detect this PID, please confirm your computer has the
240V AC
correct driver for this USB adapter (see note in the software zip file) and check the
continuity between your adapter and your PID by using a multimeter.
3). You will see the screenshot information above under "Panel View" on the left top. Click
SET button and you can change all the parameters. If you want to change multiple
parameters, please click "Tab View" button on the top. Then right click the number showing
on the right.
4). Click "Start monitor" on the top and you will see temperature chart under "Graph View".
5). Click "Record" on the top and you can use "Report" or "Backup" / "Restore" functions
later.
6). To edit ramp soak profiles, click "Program" button on the right top.
7. Manual & Download
Operation Manual (Full Version):
SYL-5352PA:
L1
https://bit.ly/5352pmanual
L2
240V AC
Or scan the following QR code by
your smartphone:
Win Software Download Link:
https://bit.ly/AuberPIDWin
Or scan the following QR code by
your smartphone:
WWW.AUBERINS.COM
Operation Manual (Full Version):
SYL-5342PA:
https://bit.ly/5342pmanual
Or scan the following QR code by
your smartphone:
Auber Instruments
5755 North Point Parkway, Suite 99
Alpharetta, GA 30022
www.auberins.com
Email: [email protected]
Tech Support: 770-569-8420
Copyright 2007-2020, Auber Instruments Inc.
All Rights Reserved.
No part of this manual shall be copied,
reproduced, or transmitted in any way without
the prior, written consent of Auber
Instruments. Auber Instruments retains the
exclusive rights to all information included in
this document.
P2/2