[Monitor Setting]
- This terminal has a monitor function.
- LINK indicator indicates the state of the
system as shown in the table on the right.
- In cases other than normal indications,
immediately turn off the power and eliminate
the associated cause then turn on again after
checking safety.
[Address Setting]
- Address numbers are used to correspond to the I/O memory map of the controller.
- Bit operation terminal
The numbers set with the address setting switch of
the terminal correspond to the addresses of the
"eject indicator lamp (output)" and the "eject check
switch (input)," respectively.
This terminal performs word-by-word data verification and update.
- You can set addresses on a point-by-point basis.
- The DIP switch value is set as the same address for the input and output.
- It is registered as the "Input unit" in registration by address automatic
recognition operation on the AnyWire Master side.
[Specifications]
Item
Rated power supply voltage
Allowable power voltage range
Ambient temperature use
Ambient humidity use
Temperature/humidity storage
Atmosphere
Noise resistance
Transmission method
Synchronization method
Transmission procedure
Transmission clock
Transmission cycle time
Connection mode
Address setting range
Number of connection points
Transmission distance
Number of simultaneously
output on points
Number of occupied data items
[Installation Location]
* Location where the unit will not be subject to vibration or shock.
* Do not install the POKA-YOKE Terminal (AU27XB-02□2-P) lengthwise.
* Where the body is not exposed to waste metal or sputter.
* Location where humidity is 35 to 85% RH, non-condensing.
* Location where the atmosphere is free of corrosive gas, ammable gas,
and sulfur.
* Location where there are no high-voltage or high-current cables.
* Location where there are no cables and controllers that generate servo,
inverter, or other high-frequency noise.
This unit does not have any special protective structure.
LINK indicator Eject indicator lamp
ADDRESS
Speci cation
24V DC (Power supply from AnyWire Master unit.)
21.6V DC - 27.6V (24V DC +15% - -10%)
Ripple 0.5Vp-p
0 - +55℃
35 - 85%RH No condensation
-20 - +70℃/35 - 95%RH
No corrosive gas
1200Vp-p (Pulse width 1 s)
DC power supply superimposed total frame/cyclic method
Frame/bit synchronization method
Dedicated protocol (AnyWire Bus)
27.8kHz (when using AB023-□□□)
5.5ms (when setting input 128 points, output 128 points)
Note ) Transmission delay time is 1 cycle to 2 cycle time.
Bus type (Multi-drop method, T-branch
method, Tree branch method)
4-wire power batch supply method
0 - 255
Up to 128 units (Connect to A027XB-02□2-P only)
Up to 100 m (0.75mm
when using our at cable)
2
128 points (When using an indication output test only)
Input 1 bit/output 1 bit
-A027XB02*2P 3/5-
Indication LED
1
2
LINK
4
8
16
32
64
128
ON
Eject indicator lamp
(Green) (Red)
Address cover
Slide it in ← direction to open.
Address setting switches are
located under the cover.
When the lever is slid in the
right direction in the posture in
the gure on the right, the
switch is turned ON.
Operate the lever without fail.
[Power Consumption/Mass]
Type
A027XB-02□2-P
■Make sure to supply power to 24V DC line for A027XB-02□2-P
from the power supply which is supplied to the AnyWire Master.
×
Do not install
the unit
lengthwise.
Indicated state
Flashing
LINK
Goes out
(Red)
Lights up
Goes out
Lights up
Lights up
Setting example
Bit
Address
1
0
・ ・
・ ・
6
・ ・
・ ・
254
* There is no speed setting.
* Set in such a manner so as not to exceed the maximum number
of transmission points including the number of own terminals.
Open
1
2
4
8
16
32
64
128
ADDRESS
Power Consumption
During standby : 10mA
While the indication is ON : 20mA
×
2
4
8
16
32
64
128
Protect the unit from
shock (no more than
0.49 G). It may cause
damage.
Monitor information
Transmission signal received
Disconnection of power
Abnormal transmission
(disconnection, short-circuit)
Eject indicaton
Goes out
Switch Setting
2
4
8 16 32 64 128
・ ・
・ ・
・ ・
・ ・
・ ・
・ ・
・ ・
○
○
・ ・
・ ・
・ ・
・ ・
・ ・
・ ・
・ ・
○
○
○
○
○
○
LINK
ON
Mass
100g
×
1
2
1
4
2
8
4
16
8
32
16
64
32
128
64
128
Do not install the
unit in a location
subject to constant
vibration.