[Various Settings]
■Types of settings
Address number setting
Teaching
■Common procedure for address writer operation
Use the Address Writer with the sensor connected to the
AnyWireASLINK master unit.
An Address Writer ARW-04 (Ver. 04-1.01 or later) or ARW-03 (Ver.
2.10 or later) is required for the operation.
For further information on the operation, refer to the product guide
for the Address Writer.
1. Connect an AnyWireASLINK slave unit to the AnyWireASLINK master unit.
Perform settings using the Address Writer with the transmission signal (DP,
DN) supplied.
Transmission
signal
2. Settings are required for all AnyWireASLINK devices.
Perform the settings with the Address Writer pointed toward the setting port
on ASLINKSENSOR.
(Hold the light emitting and light receiving parts as close as possible to the
setting port.)
* If the settings were modified in the [WRITE] mode, new settings will be reflected
after rebooting the system.
If the settings were modified in the [DIRECT WRITE] mode, new settings will be
reflected upon completion of the writing operation.
* If a multiple number of the sensors are arranged parallel, use a remote head
(ARW-RH) as well to prevent writing to a wrong terminal.
Parameter setting
Red: DP
AnyWireASLINK
master
Black: DN
24V DC*
* Use a 24V DC stabilized power supply.
Setting port
-BSK5217M**1K 6/9-
Address number setting
For address numbers, specify the leading number of the
transmission frames to be allocated to the terminal.
The address numbers of this device are set between 0 and 254.
The factory setting of the terminal is "255,"
CAUTION
which means no setting.
If the address number is set to 255, the
terminal does not perform I/O operations.
Before using the terminal, be sure to set
an address number between 0 and 254.
Teaching
Save the condition with and without a workpiece in the
ASLINKSENSOR.
[SET ON setting]
Perform this setting with a metal to be detected.
Keep a distance of at least
a half of the maximum
detection distance.
Metal
to be
detected
[SET OFF setting]
Perform this setting without a metal to be detected.
Perform the setting with the workpiece to be used in the operation.
In performing the setting, keep a distance of at least 50% of the
maximum detection distance.
If there is not sufficient difference between the conditions with and
without a workpiece, the ALM indicator will flash to notify it. In this
case, perform the setting again.
Parameter setting
■Threshold setting
This parameter determines the threshold of sensing level for
detecting the workpiece.
*
The gap in the detection conditions stored in memory in teaching is assumed to be 100%.
- Address Writer (ARW-04, ARW-03): Parameter 01
Unit
Variable
Factory Setting: BS-K5217-M18-1K: 5
0–100
%
■Hysteresis setting
This parameter determines the variation in sensing level required to
turn the detection condition OFF after it is turned ON.
- Address Writer (ARW-04, ARW-03): Parameter 02
Variable
Unit
0–100
%
Factory Setting: 5
Red: DP
AnyWireASLINK
master
Black:
DN
Red: DP
AnyWireASLINK
master
Black:
DN
BS-K5217-M30-1K: 6