Apollo REACH WIRELESS RW1500-210APO Manual de inicio rápido - Página 2

Navegue en línea o descargue pdf Manual de inicio rápido para Sistema de seguridad Apollo REACH WIRELESS RW1500-210APO. Apollo REACH WIRELESS RW1500-210APO 2 páginas. Open-area wall sounder vad
También para Apollo REACH WIRELESS RW1500-210APO: Manual de inicio rápido (4 páginas)

Apollo REACH WIRELESS RW1500-210APO Manual de inicio rápido
Apollo Fire Detectors Ltd. 36 Brookside Road, Havant, Hampshire, United Kingdom, PO9 1JR
T: +44 (0)23 9244 2706 - E: techsales@apollo-fire.com - W: www.apollo-fire.co.uk
RW1500-210APO
REACH O-A Sndr VAD Cat. W - WT Bdy (WT Fl) (W-2.5-7)
Apollo Tone
DIP Switch
Pair Number
Value
Temporal Pattern Icon
1*
0000
2*
00001
3*
00010
4*
00011
5*
00100
6*
00101
7*
00110
8
00111
9
01000
10
01001
11
01010
12
01011
13
01100
14
01101
15
01110
16
10000
*
EN 54-3 approved volume
Primary Tone (Evacuation)
Temporal Pattern
Frequencies
Description
Apollo Fire Systems
660Hz for 0.5s, 925Hz for 0.5s
Evacuate Tone
925Hz for 0.25s, 626Hz
Alternaternating warble
for 0.25s
(Hochiki & Fulleon)
Sweep (med) @ 1Hz
800Hz - 970Hz @ 1Hz
Sweep (fast) @ 9Hz
2500Hz-2850Hz @ 9Hz
Netherlands – NEN
500 – 1200Hz for 3.5s, 0.5s
2575:2000 (Dutch Slow
OFF
Whoop)
1200Hz – 500Hz Sweep 1s
German DIN 33 404
(1Hz)
Swedish Fire Signal
660Hz 0.15s ON, 0.15s OFF
Australia Fast-rise Sweep
3x (500Hz - 1200Hz for 0.5s,
(AS1670:4-2004
0.5s off), 1s off
Evacuation tone)
New Zealand Slow-rise
500Hz – 1200Hz, 3.75s
Sweep Evacuation Tone
Sweep, 0.25s OFF
(NZS 4512)
US Temporal LF (ISO
3x(970Hz 0.5s ON, 0.5s OFF),
8201) Low tone
1s OFF
US Temporal HF ISO 8201
3x(2850Hz 0.5s ON, 0.5s
High tone
OFF), 1s off
Simulated Bell -
827Hz for 16ms followed by
Continuous
990Hz for 16ms.
600Hz – 1200Hz 4s followed
Emergency Warning Siren
by 1200 – 600Hz 4s
France – AFNOR NF S 32
554Hz, 0.1s, 440Hz, 0.4s
001
Australia Evacuation
520Hz, 0.5s ON, 0.5s OFF x 3,
(AS7240-3)
1s OFF
Silent Tone (Reach
0Hz Continuous
Wireless ONLY)
Secondary Tone (Alert)
Temporal Pattern
Temporal Pattern Icon
Frequencies
Description
Apollo Fire Systems Alert
1s off, 925Hz for 1s
Tone
Continuous (Hochiki &
925Hz
Fulleon)
970Hz Continuous
Continuous
(BS5839-1:2002)
Continuous
2850Hz continuous
Continuous
825Hz continuous
Continuous
825Hz Continuous
Swedish All Clear
660Hz Continuous
Australia AS1670:4-2004
420Hz 0.625s ON, 0.625s
Alert tone
OFF
New Zealand Alert Tone
420Hz 0.625s ON, 0.625s
(NZS 4512)
OFF
Continuous
970Hz Continuous
Continuous
2850Hz continuous
827Hz for 16ms followed
Simulated Bell - Intermittent
by 990Hz for 16ms for 1s
then 1s off.
Emergency Warning Siren
1200Hz Continuous
All Clear
Continuous
970Hz Continuous
520Hz +/-5%, 0.5s ON,
Australia Alert (AS7240-3)
3.5s OFF
Silent Tone (Reach
0Hz Continuous
Wireless ONLY)
RW_QSG_AV_OA_SNDR_VAD_WT_A.5