Apollo SOTERIA UL Manual de instalación - Página 6
Navegue en línea o descargue pdf Manual de instalación para Unidad de control Apollo SOTERIA UL. Apollo SOTERIA UL 8 páginas. Nac module
GROUP ADDRESS SETTING (XP MODE ONLY)
In Group mode the NAC Module responds to an additional address referred to as the 'group address',
which is used to activate groups of NAC Modules simultaneously (The module continues to respond to its
own individual address and report its status from that address in the normal way). The group address
is selected by the four-segment dip switch S2 which is factory-set to 0000. A group address may be any
spare address within - and only within - the range 112 to 126 inclusive. The required group address is
set by moving one or more of the segments on the switch to '1' (OFF). The table shows the settings for
the group address switch.
Address
112
113
114
115
116
117
118
119
SPEAKERS
The NAC module will have the following modes available in XP and CORE system.
MODE
1
2
3
Please confirm the panel compatibility with the selected mode.
Notes:
1. In Mode 3, for installations to meet UL864 10th edition, independent external power sources shall be
used per device and must meet one of the following clauses; used power supplies must be UL 864 listed
Fire Alarm Power supplies and communicators with capability to supervise its powered output OR cable
shall be enclosed in conduit and limited to a maximum length of 20 feet.
2. Any power supply connected to the Vext I/P should be independent, regulated 24V DC, power limited
and UL listed for fire protection with battery back-up capability.
Monitoring
DIL Switch Setting
1248
1111
0111
1011
0011
1101
0101
1001
0001
Dip Switch 9
0
0
1
0: Enable
1 : Disable
Address
120
121
122
123
124
125
126
Dip Switch 10
0
1
X
DC/AC
0: DC Monitoring
1: AC Monitoring
DIL Switch Setting
1248
1110
0110
1010
0010
1100
0100
1000
Description
DC monitoring Mode
AC monitoring Mode
Unmonitored Mode
6