ADEMCO 4110DL Manual de instrucciones de instalación - Página 11
Navegue en línea o descargue pdf Manual de instrucciones de instalación para Sistema de seguridad ADEMCO 4110DL. ADEMCO 4110DL 16 páginas.
Section 5. TESTING THE SYSTEM
After installation is completed, the Security System should be carefully tested, as follows:
Test Mode
1. With the system in the disarmed state, check that all zones are intact. If a NOT READY
message is displayed, press the [ ] key to display the faulted zone(s). Restore faulted zone(s)
if necessary.
2. Enter the [Security Code] + [5] TEST. The following will occur:
•
The outside sounder will sound for 1 second.
•
A test report will be transmitted (if programmed) to the Central Station immediately. (If
the backup battery is discharged or missing, the sounder may not turn on and a LOW
BATTERY report will be transmitted with a TEST report.)
3. Fault and restore each zone.
•
The keypad will emit 3 beeps each time a contact is faulted.
•
The keypad will beep once per minute as a reminder that the system is in the Test Mode.
4. Exit this mode by entering the [Security Code] + [1] OFF .
Armed System Test
Alarm messages will be sent to the central station during the following tests. Notify them in
advance that tests will be in progress.
1. Arm the system and fault one or more zones.
2. After 15 seconds (if optional dialer delay is selected), silence alarm sounder(s) by entering the
[Security Code] + [1] OFF. Check Entry/Exit delay zones.
3. Check the keypad-panic alarms that are in the system by pressing the Panic key (key pairs
on some keypads).
•
If the system has been programmed for audible emergency, the keypad will emit a steady
alarm sound, and ALARM and [Zone Number] will be displayed. Silence the alarm by
entering the [Security Code] and pressing OFF.
•
If the system has been programmed for silent emergency, there will be no audible alarms
or displays, but a report will be sent to the central station.
4. Notify the central station when all tests are finshed, and verify results with them.
TO THE INSTALLER
Regular maintenance and inspection (at least annually) by the master and frequent testing by the
user are vital to continuous satisfactory operation of any alarm system.
The master should assume the responsibility of developing and offering a regular maintenance
program to the user as well as acquainting the user with the proper operation and limitations of the
alarm system and its component parts. Recommendations must be included for a specific program of
frequent testing (at least weekly) to insure the system's proper operation at all times.
-11-