ADEMCO VISTA-32FB Manual de inicio rápido - Página 5
Navegue en línea o descargue pdf Manual de inicio rápido para Sensores de seguridad ADEMCO VISTA-32FB. ADEMCO VISTA-32FB 5 páginas.
VISTA-32FB
Additional Features
• Notification Appliance Circuits (two):
– Programmable
– Temporal code compliant
– Individually silenceable
• Programmable on-board auxiliary relay
• SIA false alarm reduction features:
– Exit error logic
– Exit delay reset
– Cross zoning
– Call waiting defeat
– Recent close report
• Supports commercial hardwired, addressable
polling loop and wireless zones
• Hardwired zones
– Provides nine style B hardwired zones
– EOLR supervised for Fire and UL burglary installations
– Supports N.O or N.C. sensors
– Individually assignable to one or all eight partitions
– Up to 16 two-wire smoke detectors each on zone one
and two (32 total)
– Up to 50 two-wire glassbreak detectors on zone eight
• Patented addressable
polling loop technology
– Supports up to 24 two-wire
zones/points
– Global polling technology for faster processing
– Increased current draw capacity (128mA)
– Supervised by panel
– Individually assignable to partitions, notification circuit
(bell) output or aux relay
– 4,000 ft capability without the use of shielded cable
– Extender/Isolation bus module
4101SN
9500SN
Relay Module
Glassbreak Sensor
Notification Appliances
– Two-wire smoke detector zone/group expansion module
adds two or four zones
– Eight zone – Class A and B extender module
– Eight zone – Class B extender module
– One zone supervised contact monitor module
• UL Listed wireless expansion
– Supports up to 32 wireless zones/points using
5881ENHC Receiver
– Supervised by control for check-in signals
– Tamper protection for transmitters
– Individually assignable up to eight partitions
– Supports UL864/NFPA approved wireless smoke
detectors
• Event reporting
• Local printer of access or VISTA related event
• Scheduled uploading of events to central station
• Up to four doors using VistaKey
Access Control
Supported by a diverse line of ADEMCO initiating devices,
the VISTA-32FB is well suited for a variety of smaller to
medium sized applications as an integrated
fire and burglary control—including restaurants, small retail
stores and shops, churches and synagogues, strip malls,
larger residences and small factory and
warehouse environments.
• Stored events for one call retrieval
• Communication
– Phone mapping by zone response type
– Supports VIP Interactive Phone Voice Module
– Panel operation during download
– Uploading equipment list to central station
– Communication to PassPoint via Vista Gateway Module
4208U
4293SN
V-Plex Adapter
Eight-Zone
5192 Series
Expansion
Smoke
Module
Detectors
5881ENHC
V-PLEX Loop
Wireless
Commercial
Receiver
6160CR
Red Alpha
Console
VistaKey V-Plex
Access Control
Module
NAC (Bell)
4204
Circuit 4204CF
Relay
Module
}
Eight Class B Hardware Zones
4146
5140 LED
Key
Communicator
Switch
Status Module
Option
4100SM
Printer
Interface
Module
RS232
Notification Appliances
6220S Printer
Phone Line to Central Station
7720ULF Long
7845C Cellular
Range Radio
Applications
The VISTA-32FB control is well suited for a variety of
applications as an integrated fire and burglary control. A
diverse line of ADEMCO initiating devices supports this
extremely powerful control. Some of the applications
supported are: medical and professional buildings, churches
or synagogues, office buildings, schools, strip malls, larger
residences and factory or warehouse environments.
Installation
The VISTA-32FB alarm system has been designed to mount
both quickly and easily. It meets all applicable requirements
for UL commercial fire and burglary installations.
Specifications
Electrical:
• Primary power: 18VAC @ 72VA ADEMCO No. 1451
• Quiescent current draw: 350mA
• Backup battery:
– 12VDC, 7AH min to 34.4AH max
– Lead acid battery (gel type)
• Alarm power: 12VDC, 1.7A max for each notification (bell)
circuit output
• Aux. standby pwr: 12VDC, 1A max
• Total power: 2.3A at 12VDC, 3.4A at 24VDC
from all sources
• 24 hours with 1A standby load or 60 hours with 205mA
max standby load using 34.4AH battery
• Fusing: Battery input, aux. and notification (bell) circuit
outputs are protected using PTC circuit protectors. All
outputs are power limited.
4190SN
V-Plex Two-Zone
4193SN
4208SNF
Expander
4278EX Quad PIR
Serial Interface
Eight-Zone
Expansion
Module
Module
With Two Class
A Zones
5881
Wireless Receiver
ECP Bus
(Max Two)
5808LST
6139R
Smoke
32 Character
Detectors
VistaView-100
Red-Alpha
CCTV
Keypad
Switcher
4204CF
Supervised
NAC
5816
Module
Door/Window
Miniature
Transmitter
Notification
Appliance
5869
Commercial
Hold-Up Switch
VGM (PTVGM)
Supports Up To 32
Conventional Two-Wire
Smoke Detectors
Main Dialer:
• Line seize: Double Pole
• Ringer equiv.: 0.7B
• Formats: ADEMCO Low Speed, ADEMCO 4+2 Express,
ADEMCO High Speed, ADEMCO Contact ID, Sescoa and
Radionics
Cabinet dimensions:
• 14.5"H X 12.5"W X 3"D
Environmental:
• Storage temp: -10°C to 70°C
• Operating temp: 0°C to 50°C
• Humidity: 85% RH
• EMI: Meets or exceeds the following requirements:
– FCC Part 15, Class B Device
– FCC Part 68
– IEC EMC Directive
Agency Listings
• Burglary
• FCC Part 15, Class B; FCC Part 68
• UL Residential and Commercial
• UL864/NFPA Local Fire
• UL864/NFPA Central and Remote Station Fire
• UL609 Grad A Local Mercantile Premises/Local
• Mercantile Safe and Vault
• UL365 police station connected burglar alarm
• Grade AA Service (with LRR Model 7920SE)
• UL611/UL610 Central Station Burglar Alarm
• California State Fire Marshal
• FM
Manual Pull Stations
5140MPS-1*
5140MPS-2*
Q2260SN Multiplex
DUAL TEC
®
Motion Detector
4944SN
Addressable
Recessed Mount
Contact
Tamper Switch*
Flow Switch*
Low Temp Switch*
5890
Wireless PIR
5800
4209U
Series
Group Zoning
Wireless
Module
Devices
5808LST
Smoke
Detectors
Supports Up To 16
Conventional Two-Wire
Smoke Detectors
5817CB
Wireless
Commercial
Transmitter
Vista
Gateway
Module
PassPoint
*Use with 4193SN Mini-Zone Module