ABB ACH580-01 Series Manual de instalación rápida y puesta en marcha
8.
After making the additional adjustments and checking the I/O
connections, use the Diagnostics menu to make sure that the setup is
functioning correctly. In the Main menu, select Diagnostics and press
(Select) (or

Motor overload protection

The motor thermal overload protection is set to motor current and motor class curves as default. Motor thermal overload
protection can also be measured using motor temperature devices or can be estimated using a motor model defined by
parameters. To enable protection using motor model parameters or measurement devices set parameter 35.11 and
subsequent parameters through 35.55. To adjust motor class curves (default is class 20), change parameters 35.56 and
35.57.
?
Use the information key ( ) on the drive control panel for more information on setting group 35 parameters. You must set
the drive overload parameters correctly, or motor damage could occur.

Fieldbus communication

To configure the embedded fieldbus communication for BACnet MSTP, you must set at least these parameters:
Parameter
20.01 Ext1 commands
22.11 Ext1 speed ref1
28.11 Ext1 frequency ref1
58.01 Protocol enable
58.03 Node address
58.04 Baud rate
58.05 Parity
58.06 Communication
control
Other parameters related to the fieldbus configuration:

Warnings and faults

Warning Fault
Aux. code
A2A1
2281
Current calibration
A2B1
2310
Overcurrent
A2B3
2330
Earth leakage
A2B4
2340
Short circuit
-
3130
Input phase loss
).
Setting
Description
Embedded
Selects fieldbus as the source for the start and stop commands when
fieldbus
EXT1 is selected as the active control location.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as speed reference 1. Use this parameter with the vector motor
control mode.
EFB ref1
Selects a reference received through the embedded fieldbus interface
as frequency reference 1. Use this parameter with the frequency motor
control mode.
BACnet MSTP
Initializes embedded fieldbus communication.
1 (default)
Node address. There must be no two nodes with the same node
address online.
19.2 kbps (default) Defines the communication speed of the link. Use the same setting as
in the master station.
8 EVEN 1 (default)
Selects the parity and stop bit setting. Use the same setting as in the
master station.
Refresh settings
Validates any changed EFB configuration settings. Use this after
changing any parameters in group 58.
58.14 Communication loss
action
58.15 Communication loss
mode
58.16 Communication loss
time
Description
Warning: Current calibration is done at the next start.
Fault: Output phase current measurement fault.
The output current is more than the internal limit. This can also be caused by
an earth fault or phase loss.
A load unbalance that is typically caused by an earth fault in the motor or the
motor cable.
There is a short-circuit in the motor or the motor cable.
The intermediate DC circuit voltage oscillates due to missing input power
line phase.
58.101 Data I/O 1
...
58.114 Data I/O 14
12