Alpha Technologies APP60S Manual del usuario - Página 10
Navegue en línea o descargue pdf Manual del usuario para Fuente de alimentación Alpha Technologies APP60S. Alpha Technologies APP60S 15 páginas. Service power supply
2.1
Ammeter
The front panel ammeter displays output current flowing from the power module into the load.
It is extremely useful in determining the status of the plant during maintenance and trouble-
shooting. When there is no load at the output, the ammeter reads zero. When the meter
reads above the rated output of the APP60S, such as 18 or 20 Amps, an overload or short
circuit condition may exist in the load.
2.2
AC Output Fuse
The 15 Amp AC output fuse protects the load from excessive durations of short circuit current.
If the front panel ammeter reads zero, indicating no output to the load, this fuse should be
checked and replaced if necessary.
2.3
AC Input Fuse
The 12 Amp AC input fuse protects the APP60S from short circuit conditions, especially when
it is used in conjunction with a generator during outage conditions. If the unit does not come
ON when power is applied, first verify that the unit is plugged into the convenience outlet and
that the main AC circuit breaker is in the ON position. Then check the input fuse and replace
it if necessary.
2.4
AC LINE Indicator (Green)
The AC LINE indicator displays the presence of utility AC at the input. If the indicator does
not light when the unit is switched ON, first verify that the unit is plugged into the convenience
outlet and the main AC circuit breaker is in the ON position. If necessary, check the AC input
fuse and replace it if necessary.
2.5
30 / 60 VAC Switch
The 30 / 60 VAC switch is used to select the desired output voltage. For 50 Hz applications,
the switch is configured for 48 / 60 VAC.
2.6
ON / OFF Switch
The ON / OFF switch is used to apply or remove power from the APP60S.
2.7
"Jones" Connector
The APP60S "Jones" connector plugs directly into the Service Power Inserter's mating
connector to provide output power to the load. Note: The SPI's "ALT/ON" switch must be in
the "ALT" position to accept power from the APP60S.
2.8
AC Line Cord
The APP60S AC line cord plugs directly into the enclosure's convenience outlet.
5
2. APP60S FRONT PANEL
016-001-B0-002 6/97