Siemens XC10 Series Operación - Página 27
Navegue en línea o descargue pdf Operación para Unidad de control Siemens XC10 Series. Siemens XC10 Series 32 páginas. Extinguishing control unit
7
Faults / Troubleshooting
LED
Designation
N°
Color
2
Yellow Fault
3
Yellow Power supply fault
5
Yellow Earth fault
6
Yellow Disable
7
Yellow Test
8
Red
Fire alarm
9
Red
Remote transmission
11
Yellow Mechanical blocked
12
Yellow Incorrect status
Building Technologies
Fire Safety
The control panel has an extended auto-test function. In case the system indicates
a fault or is not in normal operating mode, the following table presents a listing of
possible faults with notes on possible causes.
WARNING
Always eliminate faults as soon as possible
Press simultaneously keys "1" and "3" of the numeric keypad:
-
Faults appear for 5 seconds according to the table below
State
Significance
Fixed
Multi-sector function: individual module (XCA1030) disconnected
Slow
Multi-sector function: RS485 bus (OL / SC / communication fault)
Fixed
Multi-sector function: loss of agent
Slow
Multi-sector function: loss of agent (OL / SC)
Fixed
Multi-sector function: earth fault
Fixed
Multi-sector function: actuator (OL / SC)
Slow
Multi-sector function: inter-blocking (OL / SC)
Fast
Multi-sector function: actuator + inter-blocking (OL / SC)
Fixed
Multi-sector function: selector valve (SC)
Slow
Multi-sector function: selector valve (OL)
Fast
Multi-sector function: selector valve (incorrect status)
Fixed
Multi-sector function: actuator blocked
Fixed
Multi-sector function: power supply fault
Fixed
Short circuit
Slow
Break
Fixed
Short circuit
Slow
Break
Faults / Troubleshooting
Monitored input 1
Monitored input 2
A6V10257477_c_en_--
27
2012-06