The instruction as follow:
1: Set Mode; database type: DPT_20.102 HVAC Mode;
Set value:0-OFF; 1-Fan only; 2-Cool; 3-Heat ; 4-Auto; 5-Dry
2: Set Temperature of Non Auto Mode; database type: DPT_9.001 temperature(°C).
The indoor unit temperature value corresponding to ETS temperature value:
NO.
Temp.value(℃)
1
2
3
4
5
6
7
8
3: Set Heat temperature of Auto Mode; database type: DPT_9.001 temperature(°C).
4: Set Cool temperature of Auto Mode; database type: DPT_9.001 temperature(°C).
5: Set Fan speed; data type: [5.4] DPT_Percent_U8;
Set value:1-speed1; 2-speed2; 3-speed3; 4-speed4; 5-speed5; 6-speed6;
7-speed7; 8-Auto
6: Set Heat/Cool mode switch; data type: [5.4] DPT_Percent_U8.
Set value: 0-Cool mode;1-Heat mode.
ETS value
16
06 40
17
0B 52
18
0B 84
19
0B B6
20
0B E8
21
0C 1A
22
0C 4C
23
0C 7E
NO.
Temp.value(℃)
9
10
11
12
13
14
15
9
ETS value
24
0C B0
25
0C E2
26
0D 14
27
0D 46
28
0D 78
29
0D AA
30
0D DC