Toshiba BMS-IFMB0TLR-E Manual de instalación - Página 3

Navegue en línea o descargue pdf Manual de instalación para Aire acondicionado Toshiba BMS-IFMB0TLR-E. Toshiba BMS-IFMB0TLR-E 4 páginas. Mb interface

Toshiba BMS-IFMB0TLR-E Manual de instalación
MB Interface
Configuration through micro switches
L1 L2 S1
A
B
TOSHIBA
BMS-IFMB0TLR-E
RS-485
A+
B-
S3
S4
S1 - MB Interface Setting
Switches
1 2 3 4
 x x x
 x x x
x  x x
x x  x
x x x 
S3 - Modbus slave address and baudrate
Switches
Switches
Add
Add
1 2 3 4 5 6
1 2 3 4 5 6
     
     
0
8
     
     
1*
9
     
     
2
10
     
     
3
11
     
     
4
12
     
     
5
13
     
     
6
14
     
     
7
15
* Default value
Switches
7 8
 
 
 
 
S4 - Degrees/Decidegrees (x10), temperature magnitude (ºC) and RS-485 termination resistor
Switches
1 2 3 4
 x x x
 x x x
x x x 
x x x 
* Only in the interfaces conected at both ends of the bus must be activated the termination resistor, not in the rest. The RS-485 bus can be biased through internal
jumpers JP2 and JP3. Consult the user manual for details.
WEEE Document and e-waste document for India
http://www.toshiba-carrier.co.jp/global/products/network/index.htm
S1
MB Interface Setting. This setting depend on Remote Controller connection.
ON 1 2 3 4
Please check Remote Controller connect or not.
Normal operation: At device start-up, both LEDs are on during 5 seconds.
L1 (green)
Afterwards only the green LED remains flashing (1900ms Off/100ms On). For
L2 (red)
any other indication, consult the User Manual.
Modbus slave address and Baudrate
configuration.
Configuration degrees/decidegrees (x10),
ON 1 2 3 4 5 6 7 8
ON 1 2 3 4
temperature magnitude (ºC) and RS- 485
termination resistor.
S3
S4
Connet Wired Remote Controller and/or Wireless Remote Controller (default setting)
Not Connet Wired Remote Controller and Wireless Remote Controller.
Reserve.
Reserve.
Reserve.
Switches
Switches
Add
Add
1 2 3 4 5 6
1 2 3 4 5 6
     
     
16
24
     
     
17
25
     
     
18
26
     
     
19
27
     
     
20
28
     
     
21
29
     
     
22
30
     
     
23
31
2400bps
4800bps
9600bps (default value)
19200bps
Temperature values in Modbus register are represented in degrees (x1) (default value)
Temperature values in Modbus register are represented in decidegrees (x10)
RS-485 bus without termination resistor (default value)
Internal termination resistor of 120Ω connected to RS-485 bus *
Description
Switches
Switches
Add
Add
1 2 3 4 5 6
1 2 3 4 5 6
     
     
32
40
     
     
33
41
     
     
34
42
     
     
35
43
     
     
36
44
     
     
37
45
     
     
38
46
     
     
39
47
Description
Description
Installation Manual
Switches
Switches
Add
Add
1 2 3 4 5 6
1 2 3 4 5 6
     
     
48
56
     
     
49
57
     
     
50
58
     
     
51
59
     
     
52
60
     
     
53
61
     
     
54
62
     
     
55
63
3
-EN