AERMEC ANL 040 Manual de instalación - Página 10
Navegue en línea o descargue pdf Manual de instalación para Bomba de calor AERMEC ANL 040. AERMEC ANL 040 11 páginas. Chillers; reversible heat pumps; condensing units
EN
13.
PROCEDURE FOR SELECTION OF SYSTEM TYPE
Several parameters of the MODU CONTROL board
have to be set, based on the type of system the unit is
installed.
These changes of parameters are summarised in the
table below to permit the installer to make the appro-
priate selections of the unit's electronic circuit board.
WARNING
For more information refer to the USER manual provided with the unit and available on the website
32
13.1. HOW TO MODIFY A USER MENU
PARAMETER
To access the USER setting press the key
confirm the password 000 pressing the key
display will show the parameters of the USER index
as three identifying characters; the index remains dis-
played for a second and then is replaced by the value
of the parameter it relates to.
To move to the following parameter use the arrow keys
. To modify a parameter press the key
value using the arrow keys and confirm the modifica-
tion pressing the key
key
.
ANSWER
• The unit is a cooling only model
• Radiant panels
• Fan coil units or low temperature
radiators
• Other applications
• Not installed
• Installed
• Not present
• Present
• Not present
• Present
• Not present
• Present
and
. The
, modify the
. To exit the menu press the
WHAT TO DO
• Go to question 2
• Enter in parameter StC (index 3 menu USER) with the value of 35 °C
• Enter in parameter StC (index 3 menu USER) with the value of 45 °C (default value)
• Enter in parameter StC (index 3 menu USER) with the value of 55 °C
• Go to question 3
• Enter in parameter PAN (index 9 menu INSTALLER) with the appropriate value:
• Season selection controlled from the unit circuit board
• ON/OFF control from the PR3
• Season selection controlled from the PR3
• ON/OFF control from the unit circuit board
• Season selection controlled from the PR3
• ON/OFF control from the PR3
• Go to question 5
• Enter in parameter ASA (menu INSTALLER) with the value (1)
• Go to question 5
• Enter in parameter AAS (index C menu INSTALLER) with the appropriate value (in seconds):
this parameter shows the reversing time for the three way diverting valve in the circuit for the
production of domestic hot water
• No function
• This parameter enables a digital contact ID (shown on the electrical schematic with the
reference TRA) onto which to connect an ambient thermostat with which to disable the
compressors and electric heaters. Enter in parameter
appropriate value selecting from:
1.
2.
3.
•
stops compressors and heaters if the parameter value is set to 1
•
stops compressors, pump and heaters if the parameter value is set to 2
•
pump alarm (as in the previous software version), if the parameter value is set to 3
ANL-ANLH 020-202
13.2. HOW TO MODIFY AN INSTALLER MENU
PARAMETER
To enter and modify the INSTALLER menu follow the
same procedure as the USER menu above.
1608. 6755441_02
, with the