American Standard ACONT600AF11MA Manuel d'instructions d'installation - Page 10
Parcourez en ligne ou téléchargez le pdf Manuel d'instructions d'installation pour {nom_de_la_catégorie} American Standard ACONT600AF11MA. American Standard ACONT600AF11MA 15 pages. Programmable comfort control
Installer system test
Follow the procedure below to test the heating, cooling and fan.
To begin, press and hold the
buttons until the display changes
System Test
10
Heating system
30
Cooling system
40
Fan system
70
Comfort Control
information
(for reference only)
CAUTION: EQUIPMENT DAMAGE HAZARD
Compressor protection (minimum off time) is bypassed during testing. To prevent
equipment damage, avoid cycling the compressor quickly.
and
System Status
0 Heat and fan turn off.
1 Heat turns on. Fan also turns on immediately if Function 1 or 3 is
set to "1" (see page 7).
0 Compressor and fan turn off.
1 Compressor and fan turn on.
0 Fan turns off.
1 Fan turns on.
71 Software revision number (major revisions)
72 Software revision number (minor revisions)
73 Configuration identification code (major)
74 Configuration identification code (minor)
75 Production configuration date code (week)
76 Production configuration date code (year)
System test
number
Done
Press
Press
Press
NEXT
Press
DONE
8
System
status
Next
to turn on system
to turn off system
to advance to next test
to terminate system test