CAUTION: Do not seal openings on the rooftop
flashing. Follow the installation instructions provided
with the termination being used.
Attach Bracket
Tabs to Outer
Pipe (3 places)
Secure with
Screws
Overlap
Shingles (Top
and Sides)
Figure 21 - Termination
CHASE INSTALLATIONS
Instructions for chase installations are included with the chase style
termination chosen. In a multiple chase installation, be sure to provide
adequate distance between terminations to prevent smoke spillage
from one termination to another. Terminations must be separated a
minimum of 30" center to center and stacked at a minimum vertical
height difference of 18" (see Figure 22).
Note: If a decorative shroud is to be installed, contact the manufac-
turer for specifications.
24" Min.
24" Min.
Figure 22 - Multiple Chase Installation
12
VENTING INSTALLATION Continued
10 FOOT RULE
All chimney terminations must extend a minimum of 3' above the
highest point where it passes through the roof and must be at least
2' above roof with a 10' horizontal span (see Figure 23).
RTL-8DM
Caulk
Collar
Flashing
Underlap
Shingles
FINISHING FIREPLACE
Combustible materials, such as wallboard, gypsum board, sheet rock,
drywall, plywood, etc. may directly contact sides and top front edge
at nailing flanges of fireplace face. It is important that combustible
materials do not overlap the face itself. Brick, glass, tile or other
noncombustible materials may overlap the front face provided they
do not obstruct louvered slots or any other opening. When overlap-
ping with a noncombustible facing material, use only noncombustible
mortar or adhesive appropriate for the particular installation.
18"
Min.
Typ.
www.Astria.US.com
Figure 23 - 10 Foot Rule