The following subsections provide environmental, electrical, and physical characteristics for the SPS MEDIUM POWER
Series power supplies.

ENVIRONMENTAL CHARACTERISTICS

PARAMETER
TEMPERATURE COEFFICIENT
AMBIENT TEMPERATURES
Operating
Storage
COOLING
HUMIDITY
ALTITUDE
OZONE CONCENTRATION

ELECTRICAL CHARACTERISTICS

PARAMETER
INPUT POWER
Voltage (Standard)
Voltage (Options)
Frequency
Phases
Power Factor
Efficiency
FRONT PANEL METER ACCURACY
Voltage
Current
LOAD REGULATION
Voltage
Current
LINE REGULATION
Voltage
Current
TRANSIENT RESPONSE
DOWN PROGRAMMING
STABILITY
REMOTE CONTROL/MONITOR
PARAMETER

SPECIFICATION

0.02%/°C of maximum output voltage rating for voltage set point. 0.03%/°C of
maximum output current rating for current set point.
0 to 50°C
-25° to 65°C
Internal fans; vents on sides and rear. (Units may be stacked without clearance
above or below).
95% maximum, non-condensing, 0 to 50°C; 45°C maximum wet-bulb
temperature
Operating full power available up to 5,000 feet (1,524m), derate 10% of full
power for every 1,000 feet higher; non-operating to 40,000 feet (12,192m)
Recommended long-term exposure limit is 0.1 PPM (0.2 mg/m3).
SPECIFICATION
208/220 VAC±10% (allowed range 187-242 VAC)
380/400 VAC±10% (allowed range 342-440 VAC) 440/480 VAC±10%
(allowed range 396-528 VAC)
47 to 63 Hz
3–phase, 3–wire plus ground. Not phase rotation sensitive. Neutral not used.
0.9 typical for 208/220VAC input0.78 typical for 380/400VAC input0.7 typical
for 440/480VAC input
87% typical at full load, nominal line
±0.15% of full-scale
±0.4% of full-scale
(Specified at no load to full load, nominal AC input)
0.02% of maximum output voltage
0.1% of maximum output current
(Specified ±10% of nominal AC input, constant load)
0.01% of maximum output voltage
0.05% of maximum output current
A 50% step load will recover to within 0.75% of original value within 1 ms.
With no load the output will program from 100 to 10% in less than 1.5
seconds
±0.05% of set point after 8–hr. warm-up at fixed line, load, and temperature
using remote sense
On/Off control via contact closure, 6-120 VDC or 12-240 VAC, and TTL or
CMOS switch, output voltage and current monitor, OVP limit set, summary
fault status
SPECIFICATION
3 |