Follett HCD1650RBT Manuel de démarrage rapide - Page 7

Parcourez en ligne ou téléchargez le pdf Manuel de démarrage rapide pour {nom_de_la_catégorie} Follett HCD1650RBT. Follett HCD1650RBT 8 pages. With remote air-cooled condensing unit
Également pour Follett HCD1650RBT : Manuel d'instructions d'installation (17 pages), Manuel (8 pages)

Follett HCD1650RBT Manuel de démarrage rapide

Remote condensing unit

Condensing unit installation specifications
Important specifier notes:
1. Provide front, back and side clearances
as shown.
2. The maximum refrigerant line run length is
100' (30.5 m).
1650 series – 13‑15 lbs of refrigerant
depending on line, consult manual
3. The maximum line rise above the evaporator
is 35' (10.7 m). Condensing unit above
evaporator unit – 35' (10.7 m) (installations
with rise over 20' (6.1 m) require additional
suction line s‑trap at midpoint rise).
4. The evaporator can only be mounted
a maximum of 15' (4.6 m) above the
condensing unit.
Note: The service loop is not included
when calculating length, rise or drop in
the tubing run.
Note: To connect evaporator/ice machine to rack systems, see page 3.
Remote 1650 series ice machine
=
24.00"
(61.0 cm)
48.00"
(121.9 cm)
air in
48.00"
(121.9 cm)
24.00"
(61.0 cm)
7
Form# 7040