Andivi TRC-d Manuel technique - Page 14

Parcourez en ligne ou téléchargez le pdf Manuel technique pour {nom_de_la_catégorie} Andivi TRC-d. Andivi TRC-d 19 pages.

Andivi TRC-d Manuel technique
Andivi – TRC-D – Technical Manual
READ/WRITE COILS (FUNCTION CODE 01/05/15)
Function
Register
Description
code
address
01
1
Status of room controller
Status of Protect mode
01
2
(Active only when the local PROTECT detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Status of Economy mode
01
3
(Active only when the local ECONOMY detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Status of direct control for DO1 – Cooling valve
01
4
(Active only in case of active bit 0 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 – OutC.)
Status of direct control for DO2 – Heating valve
01
5
(Active only in case of active bit 1 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 – OutC.)
Status of direct control for DO3 - Fan Stage I
01
6
(Active only in case of active bit 2 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Status of direct control for DO4 - Fan Stage II
01
7
(Active only in case of active bit 3 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Status of direct control for DO5 - Fan Stage III
01
8
(Active only in case of active bit 4 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Function
Register
Description
code
address
05/15
1
Remote room controller On/Off control
Remote control for Protect mode
05/15
2
(Active only when the local PROTECT detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Remote control for Economy mode
05/15
3
(Active only when the local ECONOMY detection is disabled. Please refer to
Modbus holding register address 6, and Engineer table parameter 03 - LOC.)
Direct control for DO1 - Cooling valve
05/15
4
(Active only in case of active bit 0 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Direct control for DO2 - Heating valve
05/15
5
(Active only in case of active bit 1 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Direct control for DO3 - Fan Stage I
05/15
6
(Active only in case of active bit 2 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Direct control for DO4 - Fan Stage II
05/15
7
(Active only in case of active bit 3 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
Direct control for DO5 - Fan Stage III
05/15
8
(Active only in case of active bit 4 of output direct control register - refer to
Modbus holding register address 38 and Engineer table parameter 35 - OutC.)
14
08/14, fw. ver. V1.2, V1.3
Definition
0: Off / 1: On
0: Protect mode not active /
1: Protect mode active
0: Economy mode not active /
1: Economy mode active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
Definition
0: Off / 1: On
0: Protect mode not active /
1: Protect mode active
0: Economy mode not active /
1: Economy mode active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active
0: Not active / 1: Active