Apollo Xpander XPA-CB-14002-APO Manuel de mise en service - Page 8

Parcourez en ligne ou téléchargez le pdf Manuel de mise en service pour {nom_de_la_catégorie} Apollo Xpander XPA-CB-14002-APO. Apollo Xpander XPA-CB-14002-APO 19 pages. Diversity loop interface module
Également pour Apollo Xpander XPA-CB-14002-APO : Manuel de mise en service (14 pages)

Apollo Xpander XPA-CB-14002-APO Manuel de mise en service

Logon procedure

Ensure batteries are installed correctly and fit the battery jumper (shown below) across both header pins.
Note: The XPander Combined Sounder (Visual Indicator) uses a DIL switch to connect the battery supply.
XPander Sounder and
Sounder/Beacon
Push the rotary select switch on the interface and release. Turn until "add new device" is shown on the menu and
push to select. On the device press the log-on button (shown below) for two seconds. A LED on the device will
flash.
Detector and Sounder logon button
PRESS HERE TO
LOGON
A five-figure code will be displayed on the interface similar to below. This is the XPander device's unique ID.
Turn the rotary select switch to 'Yes' and push to select. The menu will return to 'add new device'.
Check the device's unique ID against the ID on the label of the product to ensure that it matches.
Repeat steps to add more devices.
Press the 'Back' button on completion to return to the previous menu.
XPander MCP
XPander Detector
Base Module
MCP logon button
Input Output Unit logon button
© Apollo Fire Detectors Limited 2015
0
1
1
64
CLOSED
F-SAFE
LED
ENABLE
FAULT
INPUT 1 INPUT 2
OUTPUT 1
OUTPUT 2
XPander Combined Sounder
XPander
I/O Unit
Combined Sounder and Detector logon button
0
1
1
64
CLOSED
F-SAFE
LED
ENABLE
FAULT
INPUT 1 INPUT 2
OUTPUT 1
OUTPUT 2
A127D
8
and Detector